Permit Number: T02CM02133
Parcel: 13102008A

Address:
5401 E 29TH ST

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T02CM02133
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2002 DAN CASTRO ZONING REVIEW Approved
11/12/2002 LAITH ALSHAMI FLOODPLAIN REVIEW Denied Laith Alshami, Floodplain Comments, 11/19/2002:

1- According to the Arroyo Chico Basin Study, the 100-year Naylor Wash runoff that may potentially impact the site is 857 cfs. It also appears from the contoured aeriels that Naylor Wash 100-year surface flow splits upstream of the subject development where part of the runoff joins the local drainage in 29th street. Provide a comprehensive drainage study that models Naylor Wash 100-year runoff and determines its impact on this parcel.
2- In case it was determined that 100-year floodplain does impact the subject development, perform an encroachment analysis for the proposed improvements.
3- A floodplain use permit shall be required in case the 100-year floodplain does impact the site. There is also a $150 drainage report review fee and a $50 floodplain use permit application fee required in case the site is impacted by the floodplain.
11/12/2002 JOE LINVILLE LANDSCAPE REVIEW Denied The previous comments of 8/08/02 have not been addressed successfully. Revise the plans and obtain written approvals as necessary. In addition the MS&R covenant may be required. Plans will not be accepted for review without OK from the Landscape Section.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/27/2002 TAMI ACHONG OUT TO CUSTOMER Completed