Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T02CM02114
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/29/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
05/08/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | See redline set for additional clarification. Please return the redline set along with your next submission. E.0 1) Provide a fixture cut for "E". This fixture must have a flat flush lens pointed straight down. E.1 & E.7 1) Please provide the footing and pole design for the parking lot fixtures as part of this project. This will eliminate possible confusion and error in the field. E.4 1) Provide a circuit number for the fixtures located in rooms132,134,135,136,137,138,139, and 140. 2) Provide dual switching in accordance with 1998 IECC. E.5 1) Provide a load and circuit in Panel "L1" for circuit 19,21,23 (FC-1 and FC-2). The Total load is 4 amps at 460V 3 phase. 2) EF1 is a 1 phase 350 Watt 115V machine. The plan provides circuits P1-2,4 and a 30 amp 3P. disconnect. In addition add a load in the panel. See EF-2 circuit P1-2 for similar concerns. E.6 1) The feeder to "L1" is too small. The circuit breaker is 225 amp therefore provide a minimum 4/0 copper conductor. 99NEC 240-3, 310-16 2) The design for FC-1 and 2 does not match page E.5. See page E.5 and M-2 for appropriate design parameters. 3) Provide a fault current analysis for panel "L1" 4) Provide IECC light budget calculations. See calculations below. Calculations indicate the design does not meet minimum requirements. 5) Provide the control voltage for the CU and FC units. If it is line voltage (120 or greater) provide a control disconnect adjacent to the CU and FC starters. 99NEC 430-74. Room W/ft2 allowed Total ft2 Total W/ft2 allowed Actual W/ft2 Exercise 1.0 716 716 1440 Mech. 1.0 192 192 128 Debriefing 1.8 580 1044 768 Storage 1.0 180 180 192 Lockers 1.0 120 120 52 Corridor .8 215 172 234 2003 2424 2814 |
05/14/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approved | |
05/14/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Return air from corridor (rated) does not comply with Sec601.2IMC2000 2. Fire/smoke dampers required for rated corridors. |
05/21/2002 | PHIL SEADER | BUILDING-COMMERCIAL | REVIEW | Denied | A2.4 DOOR SCHEDULE - DOORS 137 & 138 SHOULD BE 20 MINUTE LABELED DOOR ASSEMBLIES.. A6.4 EXTEND NORTH AND EAST PARTITIONS OF JUVENILE HOLDING ROOMS AS I HOUR RATED PARTITIONS. VERIFY 1 HOUR ROOF CONSTRUCTION @ 1 HOUR RATED CORRIDOR. (CAN BE ACHIEVED WITH 2 LAYERS OF TYPE "X" GYP. BD. |
05/30/2002 | GERRY KOZIOL | WWM | REVIEW | Approved | |
05/30/2002 | MIKE BERGHUIS | FLOODPLAIN | REVIEW | Approved | |
05/31/2002 | FRANK KALINSKI | WATER | REVIEW | Approved | |
05/31/2002 | DAN CASTRO | ZONING | REVIEW | Denied | See comments for site review. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/31/2002 | TAMI ACHONG | OUT TO CUSTOMER | Completed |