Permit Review Detail
Review Status: Stopped
Review Details: COMMERCIAL NEW
Permit Number - T02CM02023
Review Name: COMMERCIAL NEW
Review Status: Stopped
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/17/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/25/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/25/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Approved | Mechanical 1. Condensor fan discharge is under a roof ( 5 ft) 2.Equipment on a concrete pad shall be 6" above grade, Sec 304.8IMC2000. |
| 09/03/2002 | HOLLY PEARCE | WATER | REVIEW | Approved | |
| 09/03/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/11/2002 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | S1) SEE PRIOR COMMENT #18 AND #19. ....................... ..PROVIDE INSPECTION PROGRAM ADDRESSING: ...... ... ..1. HIGH STRENGTH BOLTING............... .......... .......... . ..2. FIELD AND SHOP WELDING .......... ..... .......... ........ ..3. EXPANSION ANCHORS ........................... ............. . ..4. SOILS INSPECTION FOR SITE PREPARATION. ..... ..... ..5. SOILS INSPECTION FOR FOUNDATION EXCAVATION. . INDICATE WHO WILL BE DOING INSPECTIONS, etc. , PER 1994 UNIFORM ADMINISTRATIVE CODE SEC. 302.5. |
| 09/11/2002 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | COMMENTS (DATED 9/10/02) WERE FAXED TO ERIK AT ARCHITECT'S OFFICE ( 602-264-9234) 9/10/02. |
| 09/16/2002 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 09/23/2002 | JIM TATE | FLOODPLAIN | REVIEW | Approved | |
| 09/26/2002 | DAN CASTRO | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/11/2002 | ELAINE ROSE | APPROVAL SHELF | Stop |
| 07/16/2002 | ANY | OUT TO CUSTOMER | Stopped |
| 07/16/2002 | ANY | REJECT SHELF | Stopped |