Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T02CM02023
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/19/2002 | JIM EGAN | FIRE | REVIEW | Denied | |
| 04/22/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. What type of material is being used for waste lines and venting. Provide proper connection between galvanized and ? . 2. Urinal P3A missing in fixture schedule, change water demand calc's and waste fixtures. 3. Gas line going under door way does not comply with Sec1211.3UPC1994Az.Code. 4. If W.H. is installed 8ft. A.F.F. a permanent ladder will be required per Sec511.2UPC1994Az.Code. NOTE: The discharge point for the condensate line does not contain any landscaping. |
| 04/22/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Model energy code calculations are not with plan set. 2. Provide a condensate line, size and discharge location for AC6. 3. Provide manufactures data indicating that the discharge of air from AC5 will be in compliance. |
| 04/29/2002 | DAVID RIVERA | ZONING | REVIEW | Denied | approved site plan required. |
| 04/29/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/24/2002 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | SEE COMMENTS ATTACHED TO APPLICATION. |
| 05/28/2002 | FRANK KALINSKI | WATER | REVIEW | Approved | |
| 05/28/2002 | JIM TATE | FLOODPLAIN | REVIEW | Denied | Approved site plan required. |
| 05/29/2002 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/16/2002 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |