04/18/2002 MICHAEL ST. PAUL ZONING REVIEW Approved
04/18/2002 MICHAEL ST. PAUL NPPO REVIEW Passed
04/18/2002 ANY FLOODPLAIN REVIEW Approved
05/08/2002 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM02005
5/07/02
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

FOUNDATION PLANS:

1. DIMENSION THE STEM WALL THICKNESS --------MISSING AT DETAIL 1/A2

2. INDICATE MIN. 6" CLEARANCE FROM GRADE TO SILL PLATE-------DETAIL 1/A2

STRUCTURAL PLANS:

1. ROOF FRAMING PLAN INDICATES 2X6 FRAMING AT PORCHES-------DETAILS 2/A2, 3/A2 AND 5/A3 INDICATE 2X4 FRAMING, LEDGER, HANGERS---INADEQUATE----CHANGE OR SUBMIT CALCS.

2. PROVIDE BLOCKING AT ROOF DIAPHRAM FOR EDGE NAILING -DETAILS 1/A2 AND 2/A2

3. POSITIVE CONNECTION MISSING AT ALL LEDGERS-------H2.5, A35, LAGS, ETC.

4. INDICATE AND NOTE POST SIZES, DOUBLE OR TRIPLE STUDS, AND COORDINATE WITH FOUNDATION PLAN.

5. DETAIL ALL SHEAR CONNECTIONS FROM THE FOUNDATION TO THE ROOF PLYWOOD.

6. INDICATE BRACED WALL PANEL LOCATIONS

ELEVATIONS:

1. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL
VENTS NEEDED TO COMPLY.

ELECTRICAL PLANS:

1. NOTE THE LOCATION, TYPE AND AMPERAGE OF THE PANEL. NOTE THE GROUNDING AND BONDING METHOD.
BUILDING IS A DETACHED STUCTURE. WILL REQUIRED GROUND RODS OR UFER. INDICATE ON RISER DIAGRAM.


IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 112
05/08/2002 GERRY KOZIOL WWM REVIEW Denied