06/06/2002 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM01989

6/6/02 1708 N. WINSTEL BLVD. ( 2ND REVIEW )

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.
2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF
PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

FLOOR PLANS:

1. PROVIDE ALL WINDOW SIZES AND TYPES, AND DESIGNATE THE OPERABLE PORTION OF THE ONE REMAINING WINDOW IN THE BEDROOM NEXT TO THE NEW ADDITION.

2. SHOW COMPLIANCE WITH R310 PROVIDING EGRESS FROM THE BEDROOM MENYIONED IN ITEM 1 , ABOVE.

- MAXIMUM SILL HEIGHT OF 44"
- MINIMUM NET CLEAR AREA OF OPENING OF 5.7SF.
- MINIMUM NET CLEAR DIMENSIONS OF OPENING OF 24" HEIGHT BY 20" WIDTH.

3. AS DRAWN , THE FIRST RISER , BY THE PLATE , IS TO BE PRESSURE TREATED ALSO.

STRUCTURAL PLANS:

1. THE MINIMUM LIVE LOAD FOR THESE TRUSSES CAN BE FOUND IN THE I.R.C. TABLE 301.5 . JUSTIFY THE DEAD LOAD OF 10 P.S.F. DOES THE 10 P.S.F. INCLUDE THE S/R , INSULATION, AND MISCELLANY.

2. THE LUMBER VALUES YOU HAVE CITED ARE PRE-1991. PLEASE USE CURRENT VALUES.

3. PROVIDE A CROSS SECTION OF THE OVER FRAMING. 2X6 RAFTERS APPEAR TO BE OVER SPANNED A 22" X 30" OPENING FOR ACCESS AND VENTILATION INTO OVER FRAMED AREAS ( > 30 S.F. ) IS REQUIRED.


PLUMBING PLANS:

1. ¾" GAS SERVICE LINE APPEARS TO BE INADEQUATE.

ELECTRICAL PLANS:

1. IDENTIFY CIRCUIT 34 ON THE PANEL SCHEDULE.






IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVID WITT @ 791-5550 EXT. 110