Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T02CM01904
Parcel: 121030540

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T02CM01904
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. An architect is required.
05/13/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. An architect is required.
05/20/2002 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1. Service voltage is not 208 volts. Please indicate the proper served voltages.
2. Properly sequence A0 and B0 (phases) at penel schedule.
3. Indicate existing units electrical service (services to be grouped togther.
4. Indicate the bonding conductor size.
5. Indicate NEMA rating or service equipment A.C. disconnect.
6. Indicate the fixture type, lamp type, lamp wattage of the outdoor fixture.
7. Provide the conductors sizing, insulation type and the number of conductors for the overhead riser.
8. Check math on your load calculation.
9. Indicate panel A.I.C. rating.
10. Provide a circuit - 120 volt receptacle for the gas stove (elec. ignition, light and clock).
06/07/2002 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied PROVIDE DESIGN AND ANALYSIS BY AN ARIZONA REGISTERED ARCHITECT.
06/13/2002 PAUL MACHADO FLOODPLAIN REVIEW Denied See comments for site plan.
06/13/2002 DAN CASTRO ZONING REVIEW Denied See comments for site review.
06/13/2002 GERRY KOZIOL WWM REVIEW Denied
06/14/2002 INGA DAVIDSON WATER REVIEW Approved
06/14/2002 JIM EGAN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/17/2002 ELAINE ROSE OUT TO CUSTOMER Completed