Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T02CM01904
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/13/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. An architect is required. |
| 05/13/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. An architect is required. |
| 05/20/2002 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. Service voltage is not 208 volts. Please indicate the proper served voltages. 2. Properly sequence A0 and B0 (phases) at penel schedule. 3. Indicate existing units electrical service (services to be grouped togther. 4. Indicate the bonding conductor size. 5. Indicate NEMA rating or service equipment A.C. disconnect. 6. Indicate the fixture type, lamp type, lamp wattage of the outdoor fixture. 7. Provide the conductors sizing, insulation type and the number of conductors for the overhead riser. 8. Check math on your load calculation. 9. Indicate panel A.I.C. rating. 10. Provide a circuit - 120 volt receptacle for the gas stove (elec. ignition, light and clock). |
| 06/07/2002 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | PROVIDE DESIGN AND ANALYSIS BY AN ARIZONA REGISTERED ARCHITECT. |
| 06/13/2002 | DAN CASTRO | ZONING | REVIEW | Denied | See comments for site review. |
| 06/13/2002 | PAUL MACHADO | FLOODPLAIN | REVIEW | Denied | See comments for site plan. |
| 06/13/2002 | GERRY KOZIOL | WWM | REVIEW | Denied | |
| 06/14/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
| 06/14/2002 | INGA DAVIDSON | WATER | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/17/2002 | ELAINE ROSE | OUT TO CUSTOMER | Completed |