Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T02CM01900
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/22/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
| 04/22/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. Provide a Private Sewer plan prepaired by a civil engineer or a approved civil site plan for a private sewer. 2. Mop sink P9 not vented properly. 3. Provide the manufactures name and listing for the grease trap and the floor trough. Provide the size of the grease trap and if this is a grease trap, comply with Sec 1011.3UPC1994Az.Code. The vent and a clean out should be down stream of the grease trap. |
| 04/22/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Show on the plan how the mech. design complies with Chapter 4 IMC 2000. 2. Transfer air in a rated corridor to another space does not comply with Sec 601.2 IMC 2000. 3. Provide a ONE HOUR ceiling over the Type-I hood and 18' around all sides--show on M1. 4. Provide Nelson wrapid-FSB system U.L.Listing for approval. |
| 04/29/2002 | PETER MCLAUGHLIN | ZONING | REVIEW | Denied | |
| 05/22/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | GENERAL COMMENTS 1) Please return the redline set along with your next submission. This will assist in the second review. 2) See the redline set in addition to the comments for additional information. E1 1) Provide weather proof GFCI receptacles within 25' of all roof top HVAC equipment. 99NEC 210-8 and 210-63. 2) Provide a disconnect for all damper motors. 99NEC 430-102 and 430-109 3) Provide a typical interlock design for HC units and the exhaust fans. Please play particular attention to 430-74 and 430-102. 4) Provide a disconnect for the recirculating pump. 99NEC 430-102 and 430-109. 5) Provide disconnects for all kitchen equipment in accordance with 99NEC 422 part C. 6) Provide an interlock design for MAU-1 and EF-7. Please pay particular attention to 99NEC 430-74 and 430-102. E2 1) There are 12B, 2H, and 3D fixtures adjacent to circuit HB-18 that is not connected to a circuit. 2) 99NEC 220-12 requires a minimum of 150VA per 2 lineal feet of track lighting. Thus circuit HAB-24 is loaded to approximately 3562VA and HB-28 is loaded to approximately 4814VA. These loads represent the individual fixtures calculated at 125% and the track calculated at 100%. E3 1) What is total load on DPDH. The feeder is rated 510 amps. 2) Provide the conductor sizes for circuits LA1-14/16, 2/4, 7/9, 8/10. A minimum of a #10 copper conductor is required. 99NEC 310-16 |
| 05/28/2002 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 05/29/2002 | FRANK KALINSKI | WATER | REVIEW | Approved | |
| 06/05/2002 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 06/06/2002 | MVALDEZ1 | FLOODPLAIN | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/06/2002 | TAMI ACHONG | OUT TO CUSTOMER | Completed |