Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T02CM01870
Parcel: 11520198A

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T02CM01870
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2002 DAN CASTRO ZONING REVIEW Approved
04/29/2002 JIM EGAN FIRE REVIEW Approved
05/03/2002 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
05/06/2002 FRANK KALINSKI WATER REVIEW Approved
05/13/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied 1) Please describe the outside luminaires. Note all exterior lighting must conform with the light pollution ordinance and the IECC energy ordinance.
2) Provide circuit numbers for the luminaires.
3) Provide individual loads in the panel.
4) Provide wire and conduit sizes for the power outlet serving the cart.
5) Provide a complete description of the luminaires used interior to the space. In addition provide IECC light budget calculations.
6) Circuits 6/8, 10/12, 14/16, 18/20, required special purpose receptacles rated a minimum of 30 amps.
7) Provide a Midwest cooler box (or equal) for the evaporative cooler.
8) The power plan includes the words "PANEL A" on the east wall of the storage room. Please clarify.
9) Provide a minimum of a #4 copper grounding electrode system.
10) Change the reference 250-80 to 250-50 and 250-104.
11) Revise all NEC references in the specification to reflect the 1999 NEC. As an option you may remove the references that do not pertain to this of project.
05/13/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved Plumbing 1. Provide a civil site plan showing connection to the public sewer, MH Rim elev. & F.F.E. 2. Provide a waste line isometric drawing. 3. enting does not comply with Sec904.4 & 905.3 UPC 1994 Az. Code.
05/13/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved Mechanical 1. Show on the plan how the building complies with the M.E.C.
05/15/2002 MIKE BERGHUIS FLOODPLAIN REVIEW Approved
05/17/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/22/2002 CINDY AGUILAR OUT TO CUSTOMER Completed