Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T02CM01782
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/12/2003 | WILDAN | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | GENERAL COMMENTS: 1. This project has been reviewed for conformance with the 2000 IBC, 1997 UAC, 2000 IMC, 1998 IECC, and 1999 NEC codes with local modifications, and the 1994 UPC with State of Arizona amendments. Any revisions to this plan will require an additional review and approval by Willdan. ARCHITECTURAL COMMENTS: 1. No change. STRUCTURAL COMMENTS: 1. No change. PLUMBING COMMENTS: 1. The addition of gas piping to the plans for an apartment building requires plans sealed and signed by an Arizona Registered Professional Engineer or Architect, per City of Tucson policy for all commercial (triplex and above). Please have plans redone by an Arizona Registrant and resubmit. MECHANICAL COMMENTS: 1. Is gas only being supplied to the kitchen range and a log lighter in each apartment? Please clarify. ELECTRICAL COMMENTS: 1. The change from electric ranges to gas ranges indicates revisions to the electrical plans. Please coordinate and resubmit all changes to the plans affected by this change. ENERGY CODE COMMENTS: 1. No apparent change. ACCESSIBILITY COMMENTS: 1. No change. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/12/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |