Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Permit Number - T02CM01638
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/29/2002 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 03/29/2002 | PETER MCLAUGHLIN | NPPO | REVIEW | Passed | |
| 03/29/2002 | JAMES TATE | FLOODPLAIN | REVIEW | Approved | |
| 04/16/2002 | REYES ARVAYO | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T02CM01638 PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. SITE PLAN: 1. INDICATE THE LOCATION OF SEWER LINE ON THE PROPERTY, AND WHERE IT ENTERS THE BUILDING. 2. DELETE ITEMS THAT DO NOT PERTAIN TO THAT DRAWING -FOR EXAMPLE YPU DONT SHOW MECHANICAL ON FLOOR PLAN ECT, ECT. 3. NUMBER SHEETS -IN ORDER OF COSTRUCTION 4. DRAWINGS ARE TO GLUTTRERED FOUNDATION PLANS: 1. FOUNDATION LAYOUT DOESN'T MATCH FLOOR PLAN OR ROOF PLAN 2. ALL FOUNDATION HOLD-DOWNS AND ANCHOR BOLT SPACING FOR SHEAR WALLS SHALL BE SPECIFIED AND LOCATED. FLOOR PLANS: 1. LABEL ALL ROOMS AND SPACES. SHOW ALL DOORS. 2. PROVIDE ALL WINDOW SIZES AND TYPES, AND DESIGNATE THE OPERABLE PORTION OF WINDOWS, AS WELL AS THE LOCATIONS OF TEMPERED GLASS PER R308.4. 3. SHOW COMPLIANCE WITH R310 PROVIDING EGRESS FROM BEDROOMS. - MAXIMUM SILL HEIGHT OF 44" - MINIMUM NET CLEAR AREA OF OPENING OF 5.7SF. - MINIMUM NET CLEAR DIMENSIONS OF OPENING OF 24" HEIGHT BY 20" WIDTH. 4. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY ACCESSIBLE SPACE PER R807. 5. NOTE THAT BATHTUB AND SHOWER ENCLOSURES SHALL BE FINISHED PER p2710 WITH CERAMIC TILE, OR A LISTED ENCLOSURE, TO A HEIGHT OF 72" ABOVE THE DRAIN PER R702.4 AND R307.2 STRUCTURAL PLANS: 1. SPECIFY DESIGN CRITERIA ON PLANS. VALUES FOR FLOOR DEAD LOAD AND LIVE LOAD, ROOF DEAD LOAD AND LIVE LOAD. 2. PROVIDE COMPLETE ROOF AND FLOOR FRAMING PLANS. SHOW SIZE, SPACING AND SPAN OF ALL FRAMING MEMBERS, TRUSSES, JOISTS, RAFTERS, BEAMS, GLULAMS, LINTELS, HEADERS, LEDGERS AND BLOCKING. 3. SPECIFY LUMBER GRADE AND SPECIES. SPECIFY MANUFACTURER AND SERIES ON GLULAMS AND "I" JOISTS. 4. SPECIFY LATERAL SUPPORT OF TRUSSES. 5. KEY ROOF PLAN REFERANCE BACK TO DEATILS ELEVATIONS: 1. INDICATE ALL MATERIALS USED; STUCCO, CONCRETE BLOCK, GLASS BLOCK, ROOFING SYSTEMS, SIDING, VENEERS, ETC. 2. NOTE AND SPECIFY ALL ROOF SLOPES APPROPRIATE TO MATERIAL (SEE R905). 3. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL VENTS NEEDED TO COMPLY. 4. FOR THINCOAT STUCCO SYSTEMS OVER FOAM BOARD, NOTE AND SPECIFY THE ICBO EVALUATION REPORT NUMBER, SYSTEM NAME AND MANUFACTURER, NOTE AND SPECIFY THE VAPOR BARRIER. 5. FOAM INSULATION: CLARIFY YOUR COMPLIANCE WITH R318 ON THE MAIN WALLS AND THOSE WALLS TO THE ATTIC PER R318.2.3. PLUMBING PLANS: 1. NOTE AND SPECIFY ALL PIPING MATERIALS. 2. PROVIDE AN ISOMETRIC DRAWING OF WASTE LINES. SHOW SIZES OF WASTE LINES, VENTS AND REQUIRED CLEANOUTS. 3. GAS: PROVIDE THE LENGTH OF LINE TO EACH APPLIANCE, BTU DEMAND OF EACH APPLIANCE, SIZE OF EACH BRANCH, TOTAL DEMAND & TOTAL DEVELOPED LENGTH FROM METER TO MOST REMOTE APPLIANCE ON THE SYSTEM PER UPC 1217.2 4. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH 5. NOTE ON PLAN COMPLIANCE WITH WATER CONSERVATION; WATER CLOSETS 1.6 GALLONS PER FLUSH, SINKS AND SHOWERHEADS 3 GALLONS PER MINUTE. 6. DRAINAGE PIPING SERVING FIXTURES WHICH HAVE FLOOD LEVEL RIMS LOCATED BELOW THE ELEVATION OF THE NEXT UPSTREAM MAN HOLE COVER OF THE PUBLIC SEWER, SHALL BE PROTECTED FROM BACKFLOW OF SEWAGE BY A BACKWATER VALVE. NOTE AND SPECIFY ON PLANS THE LOCATION AND TYPE 8. PROVIDE PRESSURE AND TEMPERATURE RELIEF VALVE AT WATER HEATER. 9. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE INDIVIDUAL CONTROL VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE. MECHANICAL PLANS: 1. NOTE ON PLANS: MECHANICAL SHALL COMPLY WITH CHAPTERS 12 - 24 2000 IRC. 2. THE DWELLING MUST BE PROVIDED WITH HEATING CAPABLE OF MAINTAINING A ROOM TEMPERATURE OF 68 DEGREES AT A POINT 3' ABOVE THE FLOOR PER R303.6. 3. SHOW EXHAUST FAN LOCATIONS FOR BATHROOMS, WATER CLOSET COMPARTMENTS AND LAUNDRY ROOMS IN LIEU OF OPERABLE WINDOWS, PER R303.3 4. GAS APPLIANCES SHALL COMPLY WITH CHAPTER 17 COMBUSTION AIR REQUIREMENTS. DETAIL HOW. ELECTRICAL PLANS: 1. NOTE ON PLANS: ELECTRICAL WORK SHALL COMPLY WITH CHAPTERS 33 - 42, 2000 IRC. 2. NOTE THE LOCATION, TYPE AND AMPERAGE OF THE PANEL. NOTE THE GROUNDING AND BONDING METHOD. 3. DESIGNATE THE LOCATION AND CIRCUIT OF ALL REQUIRED LIGHT FIXTURES, RECEPTACLE OUTLETS, POWER OUTLETS AND SWITCHES. PROVIDE A PANEL SCHEDULE NOTING CIRCUIT NUMBER AND SIZE ALONG WITH A GENERAL DESCRIPTION. 4. PROVIDE AN EXTERIOR OUTLET AT GRADE LEVEL LOCATED AT BOTH THE FRONT AND BACK OF THE DWELLING, PER E3801.7. THESE OUTLETS SHALL BE GFI PROTECTED PER E3802.3. 5. RECEPTACLE OUTLETS SHALL BE PROVIDED AT EACH KITCHEN COUNTER SPACE WIDER THAN 12", AND SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24" FROM A RECEPTACLE OUTLET, PER E3801.4.1 6. A RECEPTACLE OUTLET SHALL BE PROVIDED ADJACENT TO THE BASIN IN EACH BATHROOM, PER E3801.6. BATHROOM OUTLETS SHALL BE ON A SEPARATE 20 AMP CIRCUIT WITH NO OTHER OUTLETS, PER E33603.4. 7. INDICATE THE LOCATION OF ALL AIR CONDITIONING AND HEATING UNITS, AIR HANDLERS, COMPRESSORS AND DISCONNECTS. 8. SUBMIT PANEL SCHEDULE SHOWING CIRCUIT AMPACITY, WIRE SIZES, PANEL SIZE AND CIRCUIT NUMBERS. 9. SUBMIT ELECTRICAL RISER DIAGRAM. 10. CLARIFY THE LOCATION AND ACCESS TO THE SUB-PANEL. 11. SHOW LOCATIONS OF SMOKE DETECTORS PER R317. NOTE THAT ALL SMOKE DETECTORS MUST BE INTERCONNECTED WITH A POWER SOURCE FROM THE BUILDING WIRING, AND SHALL BE EQUIPPED WITH BATTERY BACKUP. MODEL ENERGY CODE: 1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11. 2. CALL OUT ON THE PLANS THE "R" VALUES OF INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS AND DOORS IN CONFORMANCE WITH THE ENERGY CALCULATIONS PROVIDED. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: REYES ARVASYO @ 791-5550 EXT. 113 |
| 04/22/2002 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/26/2002 | TAMI ACHONG | OUT TO CUSTOMER | Completed |