Permit Number: T02CM01584
Parcel: 119040910

Address:
3630 S CLARK AV

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM01584
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2002 MIKE BERGHUIS FLOODPLAIN REVIEW Approved
06/17/2002 PATRICIA GEHLEN NPPO REVIEW Passed
06/17/2002 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM01584

5/3/02 3630 S. CLARK AVE.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


SITE PLAN: (NOT REQUIRED FOR MODEL PLANS)

1. LABEL THE WALL THAT IS LESS THAN 3` FROM THE PROPERTY LINE AS BEING 1-HOUR FIRE RATED. SEE R302.


FOUNDATION PLANS:


1. FOOTING WIDTHS FOR ONE-STORY, PER TABLE R403.1: ( SEE DTL. 1 ON SHT.2 )

- 16" MINIMUM; WOOD FRAME
- 19" MINIMUM; HOLLOW CONCRETE/MASONRY
- 22" MINIMUM; SOLID FULLY GROUTED/MASONRY



FLOOR PLANS:

1. NOTE SAFETY GLASS FOR THE WINDOW OVER THE BATH TUB IF NEEDED OR NOTE THE HEIGHT OF THE EDGE OF THE GLASS ABOVE THE STANDING SURFACE.


2. SHOW COMPLIANCE WITH R310 PROVIDING EGRESS FROM THE MASTER BEDROOM. ( 5840 XOX , WIDTH OF OPENING )
- MAXIMUM SILL HEIGHT OF 44"
- MINIMUM NET CLEAR AREA OF OPENING OF 5.7SF.
- MINIMUM NET CLEAR DIMENSIONS OF OPENING OF 24" HEIGHT BY 20" WIDTH.

3. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE
LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL
PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY
ACCESSIBLE SPACE PER R807.





STRUCTURAL PLANS:

1. PROVIDE AN 8" RIDGE BOARD AT THE 2X6 RAFTERS OVER THE FRONT PORCH. PROVIDE COLLARS OR CEILING JOISTS.

2. 2X4 @ 24" O.C. OVER FRAME ADJACENT THE MASTER BED ROOM APPEARS TO BE OVER SPANNED.



SECTIONS - DETAILS - MISC. NOTES:

1. BRICK TIE SPACING APPEARS TO CONFLICT WITH R703.7.6 .

2. HOW DOES THE WALL, OVERHANG INTERIOR DRYWALL AND THE VENT COMPLY WITH R302 (1-HOUR ). SEE DTLS. ¾ & ¼ .

3. 2/4 , PROVIDE A FOOTING FOR THE FRAME WALL OR BEAR THE TRUSS ON THE MASONRY WALL.


PLUMBING PLANS:

1. SIZE THE GAS LINE AFTER EACH T-FITTING FOR THE APPLIANCE TAPS.

2. THE WATER DISTRIBUTION APPEARS UNDER SIZED PER `94 U.P.C. 610 . SPECIFY THE WATER METER SIZE.

3. COMPLETE THE SIZES OF THE D.W.V. FOR THE HALL BATH UNLESS IT`S EXISTING. IF IT`S EXISTING LABEL IT AS EXISTING.

4. PROVIDE PRESSURE AND TEMPERATURE RELIEF VALVE AT WATER HEATER.

5. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE INDIVIDUAL CONTROL
VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE.

MECHANICAL PLANS:

1. GAS APPLIANCES SHALL COMPLY WITH CHAPTER 17 COMBUSTION AIR REQUIREMENTS. PROVIDE COMBUSTION AIR FOR THE WATER HEATER.

ELECTRICAL PLANS:

1. SHOW THE EXISTING ELECTRICAL DEVICES (RECEPTACLES, SWITCHES, AND LIGHTS )
OUTLET BOXES SHALL BE USED, PER E4001.6.

2. NOTE THAT ALL SMOKE DETECTORS MUST BE INTERCONNECTED WITH A POWER SOURCE FROM THE BUILDING WIRING, AND SHALL BE EQUIPPED WITH A BATTERY BACKUP.



IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110
06/17/2002 PATRICIA GEHLEN ZONING REVIEW Approved
07/08/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/11/2002 MONICA VALDEZ OUT TO CUSTOMER Completed