Review Date Reviewer's Name Type of Review Description Status Comments
03/25/2002 JIM EGAN FIRE REVIEW Approved
03/29/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Passed
03/29/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Passed
04/04/2002 PHIL SEADER BUILDING-COMMERCIAL REVIEW Approved
04/15/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied GENERAL NOTE:
Please revise the plans I have already reviewed using a cloud and delta format. Please do not submit new plans. Thank-you

PAGE E-1
1) The fixture schedule should be revised as follows: change "A1" to "B", change "B1" to "A'. This should be consistent with the remainder of the plan.
PAGE E-2
1) The conduit depth depicted in the "UNDERGROUND DUCT BANKS" detail should reflect 24" TOC. See 99NEC 300-5.
2) Hand holes are required to have a barrier where the low and high voltage conductors occupy the same enclosure. See 99NEC 725-54(a) Please revise the HANDHOLE detail.
PAGE E-4
1) It appears the A and B feeder from SCP-109 should route to VJB-10.
Page E-13
1) It appears 1004 should originate from DPL-110 not DPL-108 as shown on page 46. See tag note E on page 37 in the VJB-110 power plan.
2) It appears 702A, 702B, and 703 should originate from SCP 107 not SCP 105 as shown on page 46. See tag note 3 on page 38 in the VJB-108 power plan.
3) There are several callouts where power and instrumentation are in the same conduit. This appears to violate 99NEC 725-54(a). Please clarify the voltages or NEC classification of all conductors contained within those particular conduits.