Review Date Reviewer's Name Type of Review Description Status Comments
05/01/2002 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied SEE COMMENTS ATTACHED TO APPLICATION.
05/06/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied Second Review
SE1
1) Describe the NL fixtures. Include wattage and lamp types.
E0
1) Panel A feeder is too small for the load and the circuit breaker is too large for the feeder specified. Panel B feeder breaker is too large for the feeder specified. 99NEC 240-3 and 310-16
2) Circuits A 34, 36/38 are described as 10 amp circuit breakers. Circuit A 34 should not exceed 15 amps in order to provide short circuit protection.
E1
1) Circuit B-20 serving the sign is mislabeled in the panel on page E0.
2) Provide the conduit and conductor sizes for the AC's. Keynotes 4 and 5.
3) Provide a fused disconnect for circuit A 36/38 (EF-3) to provide both short circuit and overload protection. See keynote #9. 99Nec 430 part C.
E2
1) Keynote 13 should include a requirement for GFCI. 99NEC 210-8(b)(2).
2) All general purpose receptacles must be calculated at 180 VA minimum (no exceptions) thus B 15 =1080 VA min., and B 19=1440 min.
3) Circuit A-25 load is 7 amps thus the panel load should be 840 VA.
4) Provide a load in panel A for circuit A 23.
5) It appears circuit A 22/24, should be circuit A 20/22. See panel schedule.
6) Provide a disconnect for circuit B 8/10 (ice machine). 99NEC 422 part C.
7) Provide fused combination disconnect/starter for EC1 and EF3. In addition provide a control toggle switch located next to the combination starter to open the control circuit. 99NEC 430-74 and 102. Provide the location(s) on the plan.
8) Provide both circuit load and name for B 23.
9) Provide a minimum #10 copper conductor for circuits B 34, 35. See breaker size on page E0. In addition the duplex receptacle specified for circuit B 34 is not adequate. 99NEC 210-24 and 21(b)(3).