Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T02CM01458
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2002 PATRICIA GEHLEN ZONING REVIEW Approved
03/18/2002 PGEHLEN1 FLOODPLAIN REVIEW Approved
03/19/2002 JIM EGAN FIRE REVIEW Approved
03/19/2002 INGA DAVIDSON WATER REVIEW Approv-Cond
03/20/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
03/20/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved
03/26/2002 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied SEE COMMENTS ATTACHED TO APPLICATION.
03/27/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E0.
1) Please provide the service lateral size.
2) Provide an electrical design for circuits A-23, (27,29,31), (33,35,37), 39, (18,20), 22, 24, 26, (32,34), (36,38), (40,42) and B-21, 23, 25, 12, 14, 30, 32, 34.
3) Keynote (1) reads "Existing Exterior Light Circuits-Relocated". The same keynote appears adjacent to (2) 60 amp and (1) 100 amp circuit breakers in the Distribution Box. Please clarify.
4) Provide the feeder sizes to panels A and B.
5) Provide an electrical design for the new air conditioners. The 10 amp circuit breakers and the loads in panel A do not appear adequate.
E1
1) Clarify the type of night lights utilized. Please note they must operate 24/7/365 in order to comply with 99NEC 700-12(e).
2) With few exceptions 1998 IECC 705.2.1 requires a light design that will allow a minimum 50% uniform reduction of light levels for all areas.
E2
1) It appears Keynote 3 conduit for data is directly connected to several receptacles. Please clarify.
2) Circuit B-34 serves (4) general purpose receptacles however it is described as a 30 amp circuit for a Hot Hold on page E0.
3) Circuit A-25 is used twice-above 311V and the Auto Window.
4) Please provide a design for keynote 2.
04/03/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/18/2002 CINDY AGUILAR OUT TO CUSTOMER Completed