Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T02CM01458
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/18/2002 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
| 03/18/2002 | PGEHLEN1 | FLOODPLAIN | REVIEW | Approved | |
| 03/19/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/19/2002 | INGA DAVIDSON | WATER | REVIEW | Approv-Cond | |
| 03/20/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 03/20/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 03/26/2002 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | SEE COMMENTS ATTACHED TO APPLICATION. |
| 03/27/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | E0. 1) Please provide the service lateral size. 2) Provide an electrical design for circuits A-23, (27,29,31), (33,35,37), 39, (18,20), 22, 24, 26, (32,34), (36,38), (40,42) and B-21, 23, 25, 12, 14, 30, 32, 34. 3) Keynote (1) reads "Existing Exterior Light Circuits-Relocated". The same keynote appears adjacent to (2) 60 amp and (1) 100 amp circuit breakers in the Distribution Box. Please clarify. 4) Provide the feeder sizes to panels A and B. 5) Provide an electrical design for the new air conditioners. The 10 amp circuit breakers and the loads in panel A do not appear adequate. E1 1) Clarify the type of night lights utilized. Please note they must operate 24/7/365 in order to comply with 99NEC 700-12(e). 2) With few exceptions 1998 IECC 705.2.1 requires a light design that will allow a minimum 50% uniform reduction of light levels for all areas. E2 1) It appears Keynote 3 conduit for data is directly connected to several receptacles. Please clarify. 2) Circuit B-34 serves (4) general purpose receptacles however it is described as a 30 amp circuit for a Hot Hold on page E0. 3) Circuit A-25 is used twice-above 311V and the Auto Window. 4) Please provide a design for keynote 2. |
| 04/03/2002 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/18/2002 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |