Permit Number: T02CM01456
Parcel: 137060620

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM01456
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2002 DAVID RIVERA ZONING REVIEW Approved
03/20/2002 DAVID RIVERA NPPO REVIEW Passed
03/20/2002 ANY FLOODPLAIN REVIEW Approved
04/11/2002 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM01456
04/10/02
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE.--------PLANS AS SUBMITTED ARE HARD TO READ IN SEVERAL AREAS.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


FOUNDATION PLANS:

1. CROSS REFERENCE CALLOUTS REFER TO PAGE S-1--------THER IS NO PAGE S-1

STRUCTURAL PLANS:

1. 117/8 LPI SERIES 32 @ 16" OC ARE OVERSPANNED---------CHANGE OR SUBMIT CALCS.

2. CROSS REFERENCE CALL OUTS ON ROOF FRAMING PLAN AND CROSS SECTION PLAN INDICATE S2.1---------THERE IS NO PAGE S2.1

3. DETAIL 7 ON PAGE 8 INDICATES 3/8" ANCHOR BOLTS -------MIN. ½" REQUIRED

4. DETAIL 1 ON PAGE 8 INDICATES 12" TJI 350----CONFLICTS WITH FRAMING PLAN

5. PROVIDE CROSS SECTION OF ONE HOUR RATED FIRE WALL

6. PROVIDE CROSS SECTION OF NONBEARING EXTERIOR WALL SHOWING LEDGER CONNECTION

7. SIMPSOM AB POST BASE HAS NO UPLIFT VALUES--------USE AN ABA OR ABU TYPE BASE

ELEVATIONS:

1. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL
VENTS NEEDED TO COMPLY.

PLUMBING PLANS:

1. PROVIDE AN ISOMETRIC DRAWING OF WASTE LINES. SHOW SIZES OF WASTE LINES, VENTS AND REQUIRED
CLEANOUTS.

2. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE INDIVIDUAL CONTROL
VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE.

3. THE CITY OF TUCSON HAS NOT ADPOTED THE PLUMBING SECTION OF THE IRC 2OOO. THE CURRENT CODE BEING USED IS THE 1994 UPC WITH THE STATE AMENDMENTS. ALL PLANS MUST REFERENCE TO THIS CODE.

MECHANICAL PLANS:

1. GAS APPLIANCES SHALL COMPLY WITH 1994 UPC WITH STATE AMENDMENTS FOR COMBUSTION AIR REQUIREMENTS. DETAIL HOW.---------SIZE OF VENTS MISSING

ELECTRICAL PLANS:

1. PANEL SCHEDULE INDICATES A 200AMP SUBPANEL-------RISER DIAGRAM INDICATES 100 AMP----CLARIFY

2. RANGE ON PANEL SCHEDULE INIDICATES 50 AMPS ON A #10 WIRE------NOT TO CODE

3. A RECEPTACLE OUTLET SHALL BE PROVIDED ADJACENT TO THE BASIN IN EACH BATHROOM, PER E3801.6.
BATHROOM OUTLETS SHALL BE ON A SEPARATE 20 AMP CIRCUIT WITH NO OTHER OUTLETS, PER E33603.4.

4. INDICATE THE LOCATION OF ALL AIR CONDITIONING AND HEATING UNITS, AIR HANDLERS, COMPRESSORS
AND DISCONNECTS.

5. SHOW LOCATIONS OF SMOKE DETECTORS PER R317. REQUIRED IN ALL BEDROOMS AND AT THE ACCESS TO ALL BEDROOMS.

MODEL ENERGY CODE:

1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11.

2. CALL OUT ON THE PLANS THE "R" VALUES OF INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS
AND DOORS IN CONFORMANCE WITH THE ENERGY CALCULATIONS PROVIDED.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 112
04/22/2002 GERRY KOZIOL WWM REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
06/11/2002 MONICA VALDEZ OUT TO CUSTOMER Completed