Permit Number: T02CM01380
Parcel: 129060730

Address:
2613 E 20TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM01380
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/13/2002 MIKE BERGHUIS FLOODPLAIN REVIEW Approved
05/10/2002 PATRICIA GEHLEN NPPO REVIEW Passed
05/10/2002 PATRICIA GEHLEN ZONING REVIEW Approved
06/24/2002 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM01380

5/24/02 2613 E. 20TH

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

FLOOR PLANS:

1. LABEL ALL ROOMS AND SPACES ADJACENT TO THE ADDITIONS AND SHOW THE DOORS AND WINDOWS. SPECIFY THE MAXIMUM SILL HEIGHT OF BEDROOMS.

2. PROVIDE ACCESS TO EACH SEPARATE ATTIC THAT EXCEEDS 30SF. DESIGNATE
LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL
PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE READILY ACCESSIBLE PER R807.

3. LOCATE AND IDENTIFY SHEAR WALL TYPES AND LOCATIONS. PROVIDE NAILING SCHEDULE. ( i.e. THE BRACED WALL PANELS ADJACENT THE GARAGE DOOR , ADJACENT THE TWO 4040 MASTER BEDROOM WINDOWS )


STRUCTURAL PLANS:


1. PROVIDE INFORMATION ON 9" T.J.I. SERIES 150. DO THEY MAKE A 9" T.J.I. SERIES 150? 9 ½"?


2. PROVIDE A HEADER SCHEDULE TO IDENTIFY HEADER #1.

3. IS A FOOTER EXISTING FOR THE FRONT PORCH POST? SIZE ?


4. OVER FRAMING: IF SOLID SHEATHING IS USED ON THE LOWER TRUSSES, PROVIDE
MINIMUM OPENINGS OF 22" BY 30" FOR ACCESS AND VENTILATION INTO OVER FRAMED AREAS (>30 S.F.). IF
SOLID SHEATHING IS NOT USED ON LOWER TRUSSES, PROVIDE DETAILS FOR BRACING OF TOP CHORD OF
LOWER TRUSSES.


ELEVATIONS:

1. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL
VENTS NEEDED TO COMPLY. ( THREE AREAS )

2. THE SPACING OF THE VENEER TIES EXCEEDS THE 3.25 SQ. FT. MAXIMUM TRIBUTARY AREA ALLOWED BY R307 FOR VENEERS. ( R307.7.4.1 )



PLUMBING PLANS:

1. SHOW THE SHOWER AND THE LAVATORY VENTS.

2. IF THE 90,000 BTUH REPLACEMENT FURNACE EXCEEDS THE INPUT RATING OF THE EXISTING FURNACE , PROVIDE A GAS DIAGRAM AND TOTAL DEVELOPED LENGTH FOR THE GAS LINE.



MECHANICAL PLANS:

1. PROVIDE RETURN AIR , FOR THE FURNACE AND THE A/C , FROM THE NEW ADDITION.


ELECTRICAL PLANS:

1. PROVIDE WORKING SPACE IN FRONT OF SUB PANEL "A" IN ACCORDANCE WITH R3305.1 .

2. PROVIDE THE SIZE OF THE FEEDERS FOR SUB PANEL "A" AND THE SIZE OF THE SUB PANEL.

3. THERE ARE RECEPTACLES MISSING IN THE ARIZONA ROOM BETWEEN THE MASTER BEDROOM DOOR AND THE WINDOW. ALSO BETWEEN THE HALLWAY AND THE 6 X 3 OPENING.

4. SHOW LOCATIONS OF SMOKE DETECTORS PER R317. NOTE THAT ALL SMOKE DETECTORS MUST BE
INTERCONNECTED WITH A POWER SOURCE FROM THE BUILDING WIRING, AND SHALL BE EQUIPPED WITH
BATTERY BACKUP.


MODEL ENERGY CODE:

1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11.

2. CALL OUT ON THE PLANS THE "R" VALUES OF INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS
AND DOORS IN CONFORMANCE WITH THE ENERGY CALCULATIONS PROVIDED.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 110
06/25/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/19/2002 LISA LESNY OUT TO CUSTOMER Completed