Permit Number - T02CM01367
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2002 PETER MCLAUGHLIN NPPO REVIEW Passed
07/29/2002 PETER MCLAUGHLIN ZONING REVIEW Approved
07/29/2002 JAMES TATE FLOODPLAIN REVIEW Approved
08/23/2002 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM01367

8/26/02 2016 E.3RD ST.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

SITE PLAN: (NOT REQUIRED FOR MODEL PLANS)


1. INDICATE THE LOCATION OF GAS, WATER, ELECTRIC AND SEWER OR SEPTIC LINE ON THE PROPERTY, AND
WHERE THEY ENTER THE BUILDING. PROVIDE THE LOCATION OF YOUR WATER METER AND SEPTIC SYSTEM
IF IT EXISTS.

FOUNDATION PLANS:

1. PROVIDE A CONNECTION OF THE MASONRY WALL TO THE FOUNDATION IN DETAIL B ON 2.1 .

FLOOR PLANS:

1. PROVIDE SAFETY GLASS WITHIN 24 INCHES OF THE DOOR TO THE SCREENED PORCH .

STRUCTURAL PLANS:

1. SPECIFY DOUBLE TRIMMERS AT THE SKYLIGHTS ON THE ROOF FRAMING PLAN AND REFERENCE DETAIL 5 ON 6.1 .



SECTIONS - DETAILS - MISC. NOTES:

1. JUSTIFY THE DESIGN OF SCREEN WALLS OVER 6 FEET TALL IN DETAIL 1 ON 1.2 .

2. PROVIDE A SPECIAL INSPECTOR FOR THE EPOXY CONNECTIONS .

PLUMBING PLANS:

1. SPECIFY THE WATER METER AND THE WATER SERVICE LINE FOR THE SCREENED PORCH/STUDIO. IF THE SERVICE LINE INCLUDES THE PRIMARY RESIDENCE, INCLUDE THE TOTAL FIXTURE DEMAND OF THE PRIMARY RESIDENCE.

2. THE ½" COLD WATER SUPPLY LEAVING THE WATER HEATER MIGHT BE UNDER SIZED. RE CHECK THE SIZE WITH U.P.C.TABLE 6-4 .

ELECTRICAL PLANS:

1. THE STUDIO RECEPTACLES ARE REQUIRED TO BE WITHIN 6 FEET OF DOORWAYS AND NOT OVER 12 FEET APART.

MODEL ENERGY CODE:

1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11 .

2. CALL OUT ON THE PLANS THE "R" VALUES OF THE INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS AND DOORS IN CONFORMANCE WITH THE ENERGY CALCULATIONS PROVIDED.






IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110
08/28/2002 MVALDEZ1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/28/2002 TAMI ACHONG OUT TO CUSTOMER Completed