Permit Number: T02CM01361
Parcel: 136330870

Address:
9325 E 39TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM01361
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2002 BLANCA ESPINO FLOODPLAIN REVIEW Approved
05/17/2002 PETER MCLAUGHLIN NPPO REVIEW Passed
05/17/2002 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM01381

6/17/02 9325 E. 39 TH ST.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:


1. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.




FOUNDATION PLANS:

1. FOOTING WIDTH FOR ONE-STORY FRAME IS 16" PER R403.1.

2. PROVIDE LANDINGS AT THE TWO EXITS FROM THE DEN AREA.



SECTIONS - DETAILS - MISC. NOTES:

1. 3/2 , PROVIDE THE SHEAR VALUE FOR ΒΌ" THRU BOLTS . JUSTIFY THE 3-1/4" THRU BOLTS USED FOR THE RAFTER/RAFTER CONNECTION.


PLUMBING PLANS:

1. PROVIDE A CLEAN-OUT FOR EACH 135 DEGREES OF BEND IN THE SEWER LINE (SITE PLAN) .

2. PROVIDE A DETAIL OF THE GAS SLEEVE UNDER THE SLAB SHOWING A SEAL AT BOTH ENDS AND A VENT AT THE EXTERIOR END.

3. FIXTURE UNITS USED FOR THE WATER SUPPLY CONFLICTS WITH U.P.C. TABLE 6-3. PROVIDE THE TOTAL DEVELOPED LENGTH OF THE WATER LINE.

4. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH

ELECTRICAL PLANS:

1. THE ELECTRICAL LOAD CALCULATIONS DON`T REFLECT THE 4 NEW BASEBOARD HEATERS. SHOULD THEELECTRIC SERVICE BE UPGRADED?








IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 110
05/17/2002 PETER MCLAUGHLIN ZONING REVIEW Approved
06/19/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/20/2002 LISA LESNY OUT TO CUSTOMER Completed