Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T02CM01282
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/06/2002 | DAN CASTRO | ZONING | REVIEW | Approved | |
03/06/2002 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
03/07/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
03/08/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. Waste line isometric drawing does not comply with Sec 901.0,905.3,1011.3 UPC1994 Az. Code- provide a clean out down stream of the grease trap. 2. Part of the 3-comp sink shall be direct waste. 3.Provide clean outs per Sec 707.0 UPC 1994 Az. Code. 4. Provide the total demand length of gas line on the plan. Provide a fire system valve on the gas line serving the cooking equipment. ( see yellow tabs on bluelines) 5. Provide a water demand calculation based on Appendix A UPC 1994 Az. Code, on the plan. 6. Combustion air and relief air for the W.H. shall comply with Sec507.3.1 (c) UPC 1994 Az. Code. |
03/08/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Architect of record shall provide a complete detail of the one hour ceiling required above the type-I hood and 18 inches around all sides. 2. Kitchen exaust does not comply with Sec 506.3.13.3 IMC 2000. 3. Provide access to equipment on the roof per Sec 306.5 IMC 2000. 4. Show on the plan how the mechanical design complies with Chapter 4 IMC 2000. |
03/12/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
03/18/2002 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | SEE COMMENTS ATTACHED TO APPLICATION. |
03/19/2002 | INGA DAVIDSON | WATER | REVIEW | Approv-Cond | |
03/21/2002 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/22/2002 | DELMA ROBEY | OUT TO CUSTOMER | Completed |