Permit Number: T02CM01187
Parcel: 126042120

Address:
4349 E 5TH ST

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T02CM01187
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2002 JIM EGAN FIRE REVIEW Approved
03/05/2002 FRANK KALINSKI WATER REVIEW Approved
03/06/2002 PATRICIA GEHLEN ZONING REVIEW Approved
03/08/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied
03/08/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied
03/08/2002 PHIL SEADER BUILDING-COMMERCIAL REVIEW Denied
03/12/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E1
1) 99NEC 230-2 allows one service per building.
2) Provide TEP AFC to POA on plan, or provide note instructing contractor to have it on site for the electrical inspector.
3) Provide the service entrance conductor types and sizes.
4) The exterior fixtures must have an efficacy rating of a minimum 45 lumens per watt.
General Comment
1) Please include the plans I have already reviewed along with your next submission.
03/12/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
03/25/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/28/2002 CINDY AGUILAR OUT TO CUSTOMER Completed