02/27/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied
03/04/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied 1) NFPA 820 Table 2-2 #11 requires the entire wet well area to be designed as a NEC Class 1 Division 2 area.
2) An Electrical Engineer Registered in Arizona is required to prepare and seal the electrical design.
3) The design shall include but shall not be limited to: A complete one-line service diagram, disconnect ampacity, type, and NEMA ratings for all equipment, component short circuit current ratings for all equipment, available fault current at line terminals of service equipment and all downstream equipment, a complete fault current analysis, conduit and conductor types and sizes, overcurrent overload and short circuit protection types and sizes, equipment submittals, the location of all NEC required seals, electrical specifications, delineation of areas as classified by the NEC, complete feeder and circuitry layout, etc.
4) All equipment including motors pumps control panels, and control devices shall be listed and labeled by an OSHA approved NRTL.