Permit Number: T02CM01056
Parcel: 117042600

Address:
242 E 5TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD

Permit Number - T02CM01056
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2002 ANY FLOODPLAIN REVIEW Approved
03/19/2002 CRAIG GROSS ZONING REVIEW Approv-Cond Permit is for conversion of front unit from illegal multi-family back to single-family. Rear unit is also in violation but will be reviewed under separate permit. OK per Mike Rankin - City Attorney's office.
04/10/2002 TACHONG1 NPPO REVIEW Passed
04/10/2002 REYES ARVAYO BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM01056

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

SITE PLAN:

1. INDICATE THE LOCATION OF ELECTRIC AND SEWER LINE ON THE PROPERTY, AND WHERE THEY ENTER THE
BUILDING.

2. ONE HOUR FIRE RATED WALL WITH NO OPENINGS REQUIRED ON EXT. WALL CLOSER THAN 3'TO THE PORPETY LINE. UNLESS NEXT TO STREET ,ALLEY, EASEMENT.ECT.

FLOOR PLANS:

1. PROVIDE ALL WINDOW SIZES AND TYPES, AND DESIGNATE THE OPERABLE PORTION OF WINDOWS, AS WELL
AS THE LOCATIONS OF TEMPERED GLASS PER R308.4.

2. SHOW COMPLIANCE WITH R310 PROVIDING EGRESS FROM BEDROOMS.

- MAXIMUM SILL HEIGHT OF 44"
- MINIMUM NET CLEAR AREA OF OPENING OF 5.7SF.
- MINIMUM NET CLEAR DIMENSIONS OF OPENING OF 24" HEIGHT BY 20" WIDTH.

3. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE
LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL
PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY
ACCESSIBLE SPACE PER R807.

4. THE WALLS AND SOFFITS OF THE ENCLOSED SPACE UNDER STAIRS SHALL BE PROTECTED ON THE ENCLOSED
SIDE WITH ½" GYPSUM BOARD PER R314.8.

5. NOTE THAT BATHTUB AND SHOWER ENCLOSURES SHALL BE FINISHED PER p2710 WITH CERAMIC TILE, OR A
LISTED ENCLOSURE, TO A HEIGHT OF 72" ABOVE THE DRAIN PER R702.4 AND R307.2

6. LABLE LOWER ROOMS.

STRUCTURAL PLANS:

1. CLARIFY WHAT IS BEING DONE ON THE SUB-FLOOR --FLOOR FRAMING PLAN---YOU ALSO SHOW FRAMING FOR CEILING-HEADER ------------SEPARATE

2. PROVIDE COMPLETE ROOF AND FLOOR FRAMING PLANS. SHOW SIZE, SPACING AND SPAN OF ALL FRAMING
MEMBERS, TRUSSES, JOISTS, RAFTERS, BEAMS, GLULAMS, LINTELS, HEADERS, LEDGERS AND BLOCKING.IF APPLICABLE

PLUMBING PLANS:

1. ISOMETRIC PLUMBING LAYOUT NOT PER CODE.

2. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH

3. NOTE ON PLAN COMPLIANCE WITH WATER CONSERVATION; WATER CLOSETS 1.6 GALLONS PER FLUSH, SINKS
AND SHOWERHEADS 3 GALLONS PER MINUTE.

4. PROVIDE PRESSURE AND TEMPERATURE RELIEF VALVE AT WATER HEATER.

5. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE INDIVIDUAL CONTROL
VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE.

MECHANICAL PLANS:

1. NOTE ON PLANS: MECHANICAL SHALL COMPLY WITH CHAPTERS 12 - 24 2000 IRC.

2. SHOW EXHAUST FAN LOCATIONS FOR BATHROOMS, WATER CLOSET COMPARTMENTS AND LAUNDRY ROOMS
IN LIEU OF OPERABLE WINDOWS, PER R303.3

3. GAS APPLIANCES SHALL COMPLY WITH CHAPTER 17 COMBUSTION AIR REQUIREMENTS. DETAIL HOW.

4. IF THE HEATING OR AIR CONDITIONING EQUIPMENT IS LOCATED IN THE ATTIC, SHOW LOCATION OF ACCESS,
CATWALK AND WORKING PLATFORM. SHOW PROVISIONS FOR AND ROUTE OF SECONDARY CONDENSATE
DRAIN PER M1305.1.3.

ELECTRICAL PLANS:

1. NOTE ON PLANS: ELECTRICAL WORK SHALL COMPLY WITH CHAPTERS 33 - 42, 2000 IRC.

2. A RECEPTACLE OUTLET SHALL BE PROVIDED ADJACENT TO THE BASIN IN EACH BATHROOM, PER E3801.6.
BATHROOM OUTLETS SHALL BE ON A SEPARATE 20 AMP CIRCUIT WITH NO OTHER OUTLETS, PER E33603.4.


3.. INDICATE THE LOCATION OF CONVENIENCE OUTLET AND LIGHT SWITCH FOR ATTIC HEATING AND AIR
CONDITIONING EQUIPMENT PER E3801.11 AND E3803.4.

4. NOTE THAT LIGHT FIXTURES IN CLOTHES CLOSETS SHALL BE INSTALLED IN ACCORDANCE WITH E3903.11.

5. CLARIFY THE LOCATION AND ACCESS TO THE SUB-PANEL.MIN. 30" FRONT CLEARANCE REQUIRED

5. SHOW LOCATIONS OF SMOKE DETECTORS . NOTE THAT ALL SMOKE DETECTORS MUST BE
INTERCONNECTED WITH A POWER SOURCE FROM THE BUILDING WIRING, AND SHALL BE EQUIPPED WITH
BATTERY BACK-UP.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
REYES ARVASYO @ 791-5550 EXT. 113

Final Status

Task End Date Reviewer's Name Type of Review Description
04/16/2002 LISA LESNY OUT TO CUSTOMER Completed