Permit Number: T02CM01003
Parcel: 13303315D

Review Status: Completed

Review Details: SITE

Permit Number - T02CM01003
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/28/2002 DAVID RIVERA ZONING REVIEW Denied COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.
CODE SECTION/DEVELOPMENT STANDARD

1. Copy of the lot combination covenant prepared by the City Attorney's Office must be recorded and submitted to the Zoning Review Section prior to site plan approval.
D.S. 2-02.2.1.A.2

2. The case number for the ERZ review must be noted in the lower right corner of each sheet of the site, landscape and NPPO plans. All required elements of the ERZ as shown on the approved ERZ plan must be added to the site plan, along with date of approval and any conditions placed on that approval.
L.U.C. 2.8.6

3. All requested changes must be made to the site and landscape plans.
D.S. 2-07.2.1.A
05/30/2002 JOE LINVILLE NPPO REVIEW Denied All elements of the Native Plant Preservation Plan must be prepared by a plant professional per LUC 3.8.4.4. Please include on the plan the name of person responsible for the plant data.

Revise the transplantability and viability ratings in conformance with DS 2-15.3.2. The abbreviations and values used are not consistent with the City of Tucson standard.

The plans contain references to Pima County codes and requirements, please revise the plans to respond to City codes and requirements. LUC 3.8, DS 2-15
05/30/2002 JOE LINVILLE LANDSCAPE REVIEW Denied The floodplain and floodway lines as depicted on the site plan and native plant preservation plan must be accepted by the Engineering Section prior to approval.
The locations of temporary fencing proposed on Sheets C1, C2 and N1 should be revised for consistency as required. LUC 2.8.6
06/17/2002 ANY ENGINEERING REVIEW Denied To: Wayne E. Swan, P.E. Intertech 6089 E. Grant Rd.



SUBJECT: Tag Elementary School,
Site plan T02CM01003 (Second Review)
T14S, R15E, Section 2



RESUBMITTAL REQUIRED: Site Plan

The Site Plan (SP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.


Site Plan:


1. The Old Pueblo Archaeology Center's test excavation and preservation plan has been accepted. You must notify adjacent property owners of this decision; final decision is subject so comments from the affected neighbors. A copy of you notification should also be sent to the Development Services Director (Ernie Duarte) and the Ward 2 council office.

If you have any questions, I can be reached at 791-5550 or pmachad2@ci.tucson.az.us


Paul Machado
Senior Engineering Associate
06/17/2002 ANY FLOODPLAIN REVIEW Denied See engineering folder.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/19/2002 MONICA VALDEZ OUT TO CUSTOMER Completed