Permit Number: T02CM00912
Parcel: 126163000

Address:
4013 E TIMROD ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM00912
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2002 PATRICIA GEHLEN ZONING REVIEW Approved
02/15/2002 PATRICIA GEHLEN NPPO REVIEW Passed
02/15/2002 JAMES TATE FLOODPLAIN REVIEW Approved
03/07/2002 REYES ARVAYO BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM00912

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

SITE PLAN:

1.. INDICATE THE LOCATION OF GAS, WATER, ELECTRIC AND SEWER LINE ON THE PROPERTY, AND
WHERE THEY ENTER THE BUILDING. PROVIDE THE LOCATION OF YOUR WATER AND GAS METER.

2. CLARIFY WHAT YOU ARE DOINING - ZONING INDICATES THAT YOU ARE CONVERTING A CARPORT-TO A GUEST HOUSE.

3. IF EXISTING GUEST HOUSE PROVIDE PROOF THAT IT IS A LEGAL STRUCTURE-INCLUDING CARPOIRT ON PROPERTY LINE..

FLOOR PLANS:

1. LABEL ALL ROOMS AND SPACES. SHOW ALL DOORS.

2. PROVIDE ALL WINDOW SIZES AND TYPES, AND DESIGNATE THE OPERABLE PORTION OF WINDOWS, AS WELL
AS THE LOCATIONS OF TEMPERED GLASS PER R308.4.

3. CLARIFY LAUNDRY ROOM ? ENCLOSED OR IS THERE AN OPENING. TO OUTSIDE

STRUCTURAL PLANS:

8. DETAIL ALL CONNECTIONS AND CROSS-REFERENCE TO THE FOUNDATION AND FRAMING
PLANS:
ANCHOR BOLT SIZES AND SPACING, POST TO SILL PLATE
- LEDGERS TO MASONRY, LEDGERS TO FRAME, FRAME TO LEDGERS
- HANGER TYPES

PLUMBING PLANS:

1. NOTE AND SPECIFY ALL PIPING MATERIALS.

2. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH

3.. PROVIDE PRESSURE AND TEMPERATURE RELIEF VALVE AT WATER HEATER.

ELECTRICAL PLANS:

1. NOTE ON PLANS: ELECTRICAL WORK SHALL COMPLY WITH CHAPTERS 33 - 42, 2000 IRC.

2. A RECEPTACLE OUTLET SHALL BE PROVIDED ADJACENT TO THE BASIN IN EACH BATHROOM, PER E3801.6.
BATHROOM OUTLETS SHALL BE ON A SEPARATE 20 AMP CIRCUIT WITH NO OTHER OUTLETS, PER E33603.4.

3. ALL RECEPTACLE OUTLETS IN BATHROOMS, KITCHENS, UNFINISHED BASEMENTS, GARAGES OR CARPORTS,
AT GRADE LEVEL AND WITHIN 6' OF A WET BAR OR KITCHEN SINK SHALL HAVE GROUND FAULT CIRCUIT
INTERRUPTING PROTECTION. NOTE ON THE DRAWINGS AT EACH OUTLET REQUIRING SUCH PROTECTION,
PER E3802.



MODEL ENERGY CODE:

1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11.

2. CALL OUT ON THE PLANS THE "R" VALUES OF INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS
AND DOORS IN CONFORMANCE WITH THE ENERGY CALCULATIONS PROVIDED.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
REYES ARVAYO @ 791-5550 EXT. 113
03/14/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/18/2002 LISA LESNY OUT TO CUSTOMER Completed