Permit Number: T02CM00885
Parcel: 140270290

Address:
2917 E GANLEY RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T02CM00885
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2002 BLANCA ESPINO FLOODPLAIN REVIEW Approved
03/06/2002 JIM EGAN FIRE REVIEW Approved
03/06/2002 GERRY KOZIOL WWM REVIEW Approved
03/07/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Provide water demand calculations based on Appendix A UPC1994 Az. Code. 2. Correct yellow tabs on the plan.
03/07/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Provide Model Energy Code calculations. 2. Provide manufactures specifications showing that the area of the inside of a 4"round & a 5" round is the same as a 4" oval and a 5" oval respectively. Provide access to the up stairs furnace per Sec 306.2 IMC 2000 and the water heater per Sec 511.0 UPC 1994 Az. Code. 4. Correct yellow tab on the plan.
03/08/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Approved
03/12/2002 MARK TITUS WATER REVIEW Approved
03/12/2002 PHIL SEADER BUILDING-COMMERCIAL REVIEW Denied
03/13/2002 PATRICIA GEHLEN ZONING REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
03/14/2002 TAMI ACHONG OUT TO CUSTOMER Completed