Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T02CM00885
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/28/2002 | BLANCA ESPINO | FLOODPLAIN | REVIEW | Approved | |
| 03/06/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/06/2002 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 03/07/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. Provide water demand calculations based on Appendix A UPC1994 Az. Code. 2. Correct yellow tabs on the plan. |
| 03/07/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Provide Model Energy Code calculations. 2. Provide manufactures specifications showing that the area of the inside of a 4"round & a 5" round is the same as a 4" oval and a 5" oval respectively. Provide access to the up stairs furnace per Sec 306.2 IMC 2000 and the water heater per Sec 511.0 UPC 1994 Az. Code. 4. Correct yellow tab on the plan. |
| 03/08/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/12/2002 | MARK TITUS | WATER | REVIEW | Approved | |
| 03/12/2002 | PHIL SEADER | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 03/13/2002 | PATRICIA GEHLEN | ZONING | REVIEW | Denied |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/14/2002 | TAMI ACHONG | OUT TO CUSTOMER | Completed |