Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T02CM00841
Parcel: 104090660

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM00841
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2002 DAVID RIVERA ZONING REVIEW Approved
04/29/2002 DAVID RIVERA NPPO REVIEW Passed
04/29/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
06/04/2002 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM00841
6/4/02 633 W. LA PASADITA

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.




FOUNDATION PLANS:

1. SHOW THE FOOTING FOR THE WEST SIDE OF THE STAIRWAY.

2. PROVIDE A LANDING AT DOOR 109 ( GARAGE 3068 ) .

3. SPECIFY THE LENGTH OF THE ANCHOR BOLTS.

4. SHOW HOLD-DOWNS AND ANCHOR BOLT SPACING FOR BRACED WALL PANELS THAT ARE LESS THAN 4 FEET WIDE . SEE I.R.C. R 602.10.6 .


FLOOR PLANS:

1. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE
LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL
PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY
ACCESSIBLE SPACE PER R807.

2. LOCATE AND IDENTIFY BRACED WALL TYPES AND LOCATIONS. PROVIDE NAILING SCHEDULE.


STRUCTURAL PLANS:

1. HOW DO THE BRACED WALL PANELS AT EACH SIDE OF THE GARAGE DOOR COMPLY WITH R 602.10.6 .

2. SPECIFY THE SERIES OF THE TJI OVER THE DINING ROOM.


ELEVATIONS:

1. NOTE AND SPECIFY THE ROOF SLOPE OF THE GARAGE ROOF AND THE ROOFING MATERIAL PER R905.

2. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL
VENTS NEEDED TO COMPLY.

3. NOTE AND DIMENSION THAT THE FIREPLACE CHIMNEY MUST TERMINATE A MINIMUM OF 2' ABOVE ANY
POINT OF ROOF WITHIN 10' MEASURED HORIZONTALLY AND NOT LESS THAN 3' ABOVE THE POINT WHERE
THE CHIMNEY PASSES THROUGH THE ROOF, PER R1001.6

4. NOTE GLASS IN BATHTUB AREA SHALL BE SAFETY GLASS PER R308.4.




PLUMBING PLANS:

1. PROVIDE A TRAP PRIMER FOR THE CONDENSATE ( P-7 ).

2. GAS: PROVIDE THE LENGTH OF LINE TO THE FIREPLACE AND DESCRIBE THE "EXISTING SOURCE" THAT SUPPLIES THE GAS. IF OTHER THAN THE METER , PROVIDE THE TOTAL DEVELOPED LENGTH AND THE INPUT RATINGS OF THE OTHER APPLIANCES ON THE SYSTEM.

3. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH

4. PROVIDE A VENT FOR THE SHOWER (P-2 ).

5. PROVIDE A VENT FOR THE JACUZZI ( P-3 ). NO HORIZONTAL WET VENTS.

ELECTRICAL PLANS:


1. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED
OUTLET BOXES SHALL BE USED, PER E4001.6.


2. NOTE THAT ALL SMOKE DETECTORS MUST BE
INTERCONNECTED WITH A POWER SOURCE FROM THE BUILDING WIRING, AND SHALL BE EQUIPPED WITH
BATTERY BACKUP.


IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVID WITT @ 791-5550 EXT. 110
06/05/2002 MVALDEZ1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/10/2002 JKOZUCH1 REJECT SHELF Completed
06/10/2002 JKOZUCH1 APPROVAL SHELF Completed
06/06/2002 JKOZUCH1 OUT TO CUSTOMER Completed