Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM00755
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2002 MICHAEL ST. PAUL ZONING REVIEW Approved
02/07/2002 MICHAEL ST. PAUL NPPO REVIEW Passed
02/07/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
02/28/2002 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM00755
02/28/02
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

STRUCTURAL PLANS:

1. NOTE AND DETAIL TIE STRAPS, FRAMING ANCHORS AND JOIST HANGERS BY TYPE, SIZE AND REQUIRED
ATTACHMENT TO FRAMING MEMBERS.

2. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL
VENTS NEEDED TO COMPLY.

3. PERMITS ARE REQUIRED FOR ALL MASONRY WALLS OVER 5' IN HEIGHT--------INDICATE TOTAL LENGTH AND LOCATION OF ALL WALLS OVER 5'

4. INDICATE ON PATIO WALL DETAIL MAX. HEIGHT OF WALL
NOTE: ANY WALL OVER 6' IN HEIGHT REQUIRE ENGINEERING---FYI

5. INDICATE THICKNESS OF T111 SHEATHING ON ROOF OF PORCHES. MIN. FOR ROOF SHEATHING WITH T111 IS 5/8"

ELEVATIONS:

1. NOTE AND SPECIFY ALL ROOF SLOPES APPROPRIATE TO MATERIAL (SEE R905).
MIN. ROOF SLOPE FOR CONCRETE TILE 21/2" PER FOOT----REAR PORCH DOES NOT APPEAR TO MEET THIS REQUIREMENT
CHECK ROOF SLOPES OF ALL PORCHES THEY DO NOT APPEAR TO BE 3/12 AS CALLED OUT

PLUMBING PLANS:

1. CITY OF TUCSON HAS NOT ADOPTED THE PLUMBING SECTION OF THE IRC 2000 CODE. THE CURRENT PLUMBING CODE IS THE 1994 UPC WITH THE STATE AMENDMENTS. CHANGE ALL REFERENCES.NOTE AND SPECIFY ALL PIPING MATERIALS.

2. YARD WATER LINE IS UNDERSIZED FOR A ¾" METER-------ALSO DEVELOPED LENGTH MUST INCLUDE DISTANCE TO FURTHEST FIXTURE IN THE HOUSE

3. A TRAP PRIMER IS REQUIRED AT FLOOR DRAIN AT LAUNDRY SINK-----ALSO LAUNDRY SINK MUST DRAIN INTO WASTE LINE----NOT INDICATED

4. TWO TRAPS ON A SINGLE DIRTY ARM NOT ALLOWED AT MASTER BATH SHOWER AND LAV.

5. NOTE ON PLAN COMPLIANCE WITH WATER CONSERVATION; WATER CLOSETS 1.6 GALLONS PER FLUSH, SINKS
AND SHOWERHEADS 3 GALLONS PER MINUTE.

6. PROVIDE PRESSURE AND TEMPERATURE RELIEF VALVE AT WATER HEATER.

MECHANICAL PLANS:

1. GAS APPLIANCES SHALL COMPLY WITH CHAPTER 17 COMBUSTION AIR REQUIREMENTS. DETAIL HOW.
INDICATE SIZE OF VENTS

ELECTRICAL PLANS:


1. A RECEPTACLE OUTLET SHALL BE PROVIDED ADJACENT TO THE BASIN IN EACH BATHROOM, PER E3801.6.
BATHROOM OUTLETS SHALL BE ON A SEPARATE 20 AMP CIRCUIT WITH NO OTHER OUTLETS, PER E33603.4.
CANNOT BE WITH RECEPT. IN FURNACE ROOM NOR WITH SINK IN GARAGE

2. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED
OUTLET BOXES SHALL BE USED, PER E4001.6.

3. NOTE THAT LIGHT FIXTURES IN CLOTHES CLOSETS SHALL BE INSTALLED IN ACCORDANCE WITH E3903.11.

4. ADD THE FOLLOWING NOTE: "ALL DWELLINGS FOR WHICH PERMITS ARE ISSUED AFTER JANUARY 1, 2002
SHALL BE PROVIDED WITH ARC-FAULT CIRCUIT INTERRUPTER PROTECTION PER NEC ARTICLE 210-12"

5. CLARIFY THE LOCATION AND ACCESS TO THE SUB-PANEL.
MIN. 30" SIDE CLEARANCE AND MIN. 36" FRONT CLEARANCE

6. SHOW LOCATIONS OF SMOKE DETECTORS PER R317. NOTE THAT ALL SMOKE DETECTORS MUST BE
INTERCONNECTED WITH A POWER SOURCE FROM THE BUILDING WIRING, AND SHALL BE EQUIPPED WITH
BATTERY BACKUP.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 112
03/05/2002 GERRY KOZIOL WWM REVIEW Approved