Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T02CM00637
Parcel: 12620001A

Address:
3455 E ZOO CT

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02CM00637
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
3/18/2003
Zoning can not review and approve building plans until the structural reviewers have approved the building plans.
03/24/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/24/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The building sewer is to be designed to the UPC / State Plumbing Code. Note #1 on sheet C2.0 references the "Pima County / City of Tucson Standard Specifications for Public Improvements"; this is not the same as the UPC / State Plumbing Code.
2. Note size of vent for drinking fountain, P-7C.
3. Provide upper terminal cleanout at P-7C. Reference Section 707.4, UPC.
4. Provide cleanout for lavatory P-1A located in Toilet 117. Reference Section 707.4(1), UPC.
5. Clarify layout of gas piping at the mechanical room. The 2" line from the meter has a tee overhead with one branch running to the east to service the water heater and boiler and the other branch running to the west. The west branch is not sized and it is not clear where it is going.
03/25/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
04/09/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/14/2003 TAMI ACHONG OUT TO CUSTOMER Completed