Permit Number: T02CM00576
Parcel: 121113250

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T02CM00576
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2002 JIM EGAN FIRE REVIEW Approved
02/04/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
02/04/2002 DAVID RIVERA ZONING REVIEW Approved
02/04/2002 ANY FLOODPLAIN REVIEW Approved
02/04/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved
02/05/2002 RSCHULE1 ELECTRICAL-COMMERCIAL REVIEW Denied E-1
1) Circuits A-34,36,38,40,35,36 are indicated as a home run on the plan. The circuitry includes circuit 37. Please clarify.
2) It appears home run circuit A-24 should include circuit A-26. In addition the receptacles should be equally distributed between the circuits in order to coincide with the loads in the panel.
E-2
1) Circuits A12,14,16 are overloaded by a factor of nearly 3.
E-3
1) The A/C #3 description indicates a 240V/1phase unit above gutter #1.
2) The load calculations for gutter #1 indicates a load for panel S, however I couldn't locate a panel S on the gutter. Please clarify.
3) Provide a fault current analysis for the worst case alternate condition.
02/14/2002 TGRIFFU1 WWM REVIEW Needs Review
02/14/2002 TGRIFFU1 WATER REVIEW Needs Review
02/14/2002 TGRIFFU1 BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/14/2002 TGRIFFU1 OUT TO CUSTOMER Completed