Permit Number: T02CM00573
Parcel: 13803031M

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T02CM00573
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2002 PATRICIA GEHLEN ZONING REVIEW Approved
02/04/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
02/06/2002 JIM EGAN FIRE REVIEW Approved
02/11/2002 PHIL SEADER BUILDING-COMMERCIAL REVIEW Denied
02/11/2002 MARK TITUS WATER REVIEW Approved
02/12/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied
02/12/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied
02/21/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied 1) Provide a disconnect for the ΒΌ HP fan on the roof on page E2.0
2) Provide #10 cu for the WH in the panel schedule circuit 34,36,38 on page E2.0.
3) Connect all EM/Exit lights to the un-switched side of the circuit in the area served. 99NEC 700-12(e). See page E3.0
4) PLEASE MAKE HANDWRITTEN CHANGES ON THE DOCUMENTS SUBMITTED DO NOT SUBMIT NEW PLANS.
02/26/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/06/2002 TAMI ACHONG OUT TO CUSTOMER Completed