Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T02CM00573
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/04/2002 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
| 02/04/2002 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 02/06/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
| 02/11/2002 | PHIL SEADER | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 02/11/2002 | MARK TITUS | WATER | REVIEW | Approved | |
| 02/12/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | |
| 02/12/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | |
| 02/21/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1) Provide a disconnect for the ΒΌ HP fan on the roof on page E2.0 2) Provide #10 cu for the WH in the panel schedule circuit 34,36,38 on page E2.0. 3) Connect all EM/Exit lights to the un-switched side of the circuit in the area served. 99NEC 700-12(e). See page E3.0 4) PLEASE MAKE HANDWRITTEN CHANGES ON THE DOCUMENTS SUBMITTED DO NOT SUBMIT NEW PLANS. |
| 02/26/2002 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/06/2002 | TAMI ACHONG | OUT TO CUSTOMER | Completed |