Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T02CM00555
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/04/2002 | ANY | FLOODPLAIN | REVIEW | Approved | |
| 02/05/2002 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | 4/18 Zoning- building plans may not be approved until the approved development and landscape plans are included in the submittal package |
| 02/05/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/01/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. Provide an approved private sewer or public sewer plan indicating where the attachment of this building sewer will be. Provide the size of the existing sewer line and the slope of same on A-2. Provide the building F.F.E. and the size of the new sewer line and slope of same on A-2. NOTE: Minimum print size is 10pt for all plans. FIX. 2. Show on the site plan where the popable water comes from, size of pipe, meter, etc. 3. Provide the listing and installation standards for the OATEY sure-vent air admittance valves. NOTE: Any heating equipment will be part of this permit. NOTE: Floor drain in the equipment room CAN NOT be used for back washing of pool water. |
| 03/01/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Provide comb/relief air for any gas fired equipment, show sizes on the plan. |
| 03/01/2002 | TOM CLARK | WATER | REVIEW | Approved | |
| 03/05/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | E-1 SERVICE 1) The ground rod spacing should note 6' minimum. 99NEC 250-56 2) Provide wireway size. 3) Do not include an equipment ground in the service lateral. The equipment ground and neutral would be in parallel thus making the ground a current carrying conductor. 4) Provide TEP AFC to POA . The downstream panel boards must be listed/labeled series rated for the highest fault at their line terminals. This must be noted along with the line terminal fault current on the plan. 5) Only 1 feeder may be utilized to serve the pool equipment room and the restrooms. An additional feeder is required to serve the storage ramada area. This feeder may originate from the panel in the pool equipment room or the service. In addition there must be a main breaker and grounding electrode system at each ( pool/restroom and storage/ramada) buildings. 99NEC 225-30, 31, 32, 36 and 250-32. 6) Provide the line side conductor sizes for the service disconnects. Note: If an equipment bonding conductor on the line side of the disconnect is installed you must use 99NEC 250-66 for appropriate sizing. See 99NEC 250-102(c). E-3 1) The piping serving the 'C' fixtures must be a minimum of 5' from the inside wall of the pool. 99NEC 680-10 2) Indicate by note a separate building and electrical permit for the pool is required. 3) Indicate by note that the junction box and wiring for the pool cover be located a minimum 5' from the inside wall of the pool per 99NEC 680-269(a) 4) Indicate by note the #2 copper bond be routed back to the pool equipment and pool cover motor per 99NEC 680-22(a)(4). 5) Provide a complete design consistent with 99NEC 690 in every detail for the photo voltaic system, or indicate by note that a separate permit must be obtained. |
| 03/11/2002 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 03/12/2002 | MVALDEZ1 | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/18/2002 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |