Permit Number: T02CM00533
Parcel: 12402008A

Address:
1801 E 1ST ST

Review Status: Completed

Review Details: 3RD PARTY REVIEW-REVISION/OTHER

Permit Number - T02CM00533
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied SCOPE OF REVIEW:

The scope of this review covers revisions to Mechanical and Plumbing . All features were checked only to the extent allowed by the submittal provided. All portions of the project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

MECHANICAL:

q Sketches SK-3 and SK-4 of 4 removed the secondary condensate lines from the detailed fan coils. These units because of their location require secondary condensate drain systems [2000 IMC Sec. 307.2.3] unless the auxiliary drain pan has a level detection device that will shut of the equipment [2000 IMC Sec. 307.2.3 Method 3]. Please clarify.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/01/2003 ELAINE ROSE OUT TO CUSTOMER Completed