Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2003 Martin Haeberle BUILDING-COMMERCIAL REVIEW Denied Upon receipt of the complete construction drawings and calculations the following discrepancies exist:

1.Construction drawings indicate not for construction
2. Letter from engineer indicates a minimum 12" into soil footing, plans and other details indicate 4".
3. Calculations indicate soil pressure of 1521psf but cover letter states 1500psf
4. Calculations do not include a complete lateral analysis.

Revise plans/ calculations to resolve the aforementioned discrepancies in the plans.