Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T02BU03072
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/16/2003 | Martin Haeberle | BUILDING-COMMERCIAL | REVIEW | Denied | Upon receipt of the complete construction drawings and calculations the following discrepancies exist: 1.Construction drawings indicate not for construction 2. Letter from engineer indicates a minimum 12" into soil footing, plans and other details indicate 4". 3. Calculations indicate soil pressure of 1521psf but cover letter states 1500psf 4. Calculations do not include a complete lateral analysis. Revise plans/ calculations to resolve the aforementioned discrepancies in the plans. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/25/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 07/17/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |