Permit Number: T02BU03007
Parcel: 134211430

Review Status: Completed

Review Details: POOL/SPA

Permit Number - T02BU03007
Review Name: POOL/SPA
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/30/2002 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02BU03007
1/06/02
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

SITE PLAN:

1. CLEARLY INDICATE LOCATION OF THE BARRIER AND ENCLOSURE ON SITE PLAN.

POOL DESIGN PLAN

1. CLEARLY INDICATE LOCATION OF THE BARRIER AND ENCLOSURE ON THE PLAN. THE SITE PLAN INDICATES A CARPORT ON THE SOUTH SIDE OF THE POOL, THE POOL PLAN DOES NOT. INDICATE ANY OPENINGS, WINDOWS, OR DOORS ON THE EXISTING STRUCTURE AND HOW CODE COMPLIANCE FOR BARRIER REQUIREMENTS WILL BE MET.

2. 80 AMP SUBPANEL WITH #6 WIRE DOES NOT MEET CODE.

3. 11/2 HP PUMP MOTOR WILL NOT WORK ON #14 WIRE [15 AMP CIRCUIT]

4. INIDCATE REQUIRED 2 RETURN OUTLETS MIN. 3' APART AT BOTTOM OF POOL.

5. GAS LINE SIZE IS INADEQUATE FOR LENGTH OF RUN TO BTU'S.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 1112
12/30/2002 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied ... T02BU03007 ... 6951 E. MALVERN PLACE .. 12/30/02 ... ... DGL ............................................................................ .1. DESIGN TO CONFORM TO 'INTERNATIONAL BUILDING CODE ' vs 'UNIFORM BUILDING CODE' CITED IN STRUCTURAL CALCULATIONS AND DRAWINGS, REVISE. . .2. CLARIFY SUBMITTAL IS COMPLETE, WHERE IS DRAWING #S-2 OF 3, EXPLAIN ? ...................................... .3. MINIMUM FONT SIZE 10 (TEN) POINT FOR PERMIT DOCUMENTS, VERIFY/REVISE. ........................................ .4. WHY WERE 4 (FOUR) S-1 DRAWINGS SUBMITTED ? ... .5. PROVIDE COMPLETED 'CODE REVIEW CHECKLIST, ATTACHED. .....................................................................

Final Status

Task End Date Reviewer's Name Type of Review Description
01/07/2003 ELAINE ROSE OUT TO CUSTOMER Completed