Permit Number: T02BU02980
Parcel: 141148170

Review Status: Completed

Review Details: GRADING

Permit Number - T02BU02980
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2003 PATRICIA GILBERT NPPO REVIEW Denied An approved site plan is required prior to grading plan approval.

Please submit an approved copy of the NPPO plan or exception application to NPPO.

A pre-permit inspection may be required.
01/07/2003 LOREN MAKUS NPDES REVIEW Denied As part of a larger common plan of development or sale, this project must obtain coverage under the construction general permit. Please submit three copies of the stormwater pollution prevention plan with signed certifications and notice of intent.
01/07/2003 MICHAEL ST. PAUL ZONING REVIEW Denied Engineering, NPPO and NPDES approvals are required before Zoning review.
12/31/2002 PAUL MACHADO ENGINEERING REVIEW Denied To: Steve Gregor, P.E. President
1660 N. Alvernon Way

RESUBMITTAL REQUIRED: Grading Plan

The Grading Plan (GP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:

1. The grading plan cannot be approved until the development plan is approved.
2. A cross access agreement is needed to construct the driveway.
3. Construction key note #3 calls out a 3" reveal vertical curb, what is the length of the curb?
4. Add note: "Depress all landscaped areas a maximum of 6" for water harvesting"
5. Provide/Add the basin maintenance responsibility notes per 2.3.1.6 C 1 and 2.
6. Where is construction key note no. 25 used?
7. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, add a general note indicating sidewalk scuppers (per COT/SD) will be used when the roof scuppers locations have been designed.

If you have any questions, I can be reached at 791-5550, or pmachad2@ci.tucson.az.us
Paul Machado
Senior Engineering Associate
12/31/2002 ANY FLOODPLAIN REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/08/2003 CINDY AGUILAR OUT TO CUSTOMER Completed