Permit Number: T02BU02964
Parcel: Unknown

Address:
3630 E FELIX BL

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02BU02964
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/11/2003 Elizabeth Eberbach ENGINEERING REVIEW Approved DATE: September 15, 2003
SUBJECT: Drexel Manor 4th Submittal Grading Plan Engineering Review
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBER: T02BU02964

SUMMARY: The response letter, revised Grading Plan, a final copy of the final Drainage Report, and the geotechnical report addendum were received by Engineering on September 2, 2003. Engineering Division recommends approval of the Grading Plan. The Drainage Report dated 2-17-03 is approved for Grading Plan purposes only. When picking up the grading permit, submit the grading bond for $41,500. An outline for the specifics regarding basin post-construction percolation testing referred to in General Note 14b is available. If you have questions, or would like to set up an optional pre-construction meeting, please call me at 791-5550, extension 2204.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Section
Development Services
09/11/2003 Loren Makus NPDES REVIEW Approved
09/29/2003 Joseph Linville NPPO REVIEW Approved NPPO pre-permit inspection is required, to schedule please call 791-5550, ext. 1118. - PG
10/01/2003 Patricia Gehlen ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/06/2004 SUE REEVES OUT TO CUSTOMER Completed
10/01/2003 ANGIE SHOFFSTALL APPROVAL SHELF Completed