Review Status: Completed
Review Details: GRADING
Permit Number - T02BU02957
Review Name: GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/10/2002 | JIM TATE | ENGINEERING | REVIEW | Approved | GRADING 1. Indicate a Location map (3" =1 mile) and north arrow. 2. Show a Legend showing all symbols/lines used. 3. Indicate different line weights to identify symbols. 4. The plan indicates nine trees, four of which have the word "TREE" outside the circle. Please relocate the word "TREE" inside the circle. 5. Indicate cut and fill quantities in cubic yards. 6. Indicate basis of elevation and basis of bearing - provide City of Tucson Bench Mark datum with field book & page number. |
| 12/10/2002 | BLANCA ESPINO | NPDES | REVIEW | Passed | |
| 12/10/2002 | BLANCA ESPINO | FLOODPLAIN | REVIEW | Approved | |
| 12/16/2002 | PATRICIA GILBERT | NPPO | REVIEW | Approved | Please add a general note that all grading will conform to Development Standard 9-04 Hillside Development Site Improvement. Portions of the site to be left ungraded (undisturbed by construction) temporary fencing is required to be installed at the grading limits in order to prevent encroachment to the undisturbed portion. Refer to DS 9-04.3.1.A.2. Pre-permit inspection will be required to inspect temporary fencing. To schedule please call 791-5640, ext. 1140. |
| 12/16/2002 | PATRICIA GEHLEN | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/03/2003 | LISA LESNY | OUT TO CUSTOMER | Completed |