12/10/2002 PAUL MACHADO ENGINEERING REVIEW Denied To: Kurt McAloney
Rocking M Building and Development
7301 E. Twenty Second Street

SUBJECT: Lot 127 of Rancho Cancion West
T02BU02940 (First submittal)
T14S, R15E, Section 36

RESUBMITTAL REQUIRED: Grading Plan

The Grading Plan (GP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:

1. Grading plan clearly marked "GRADING PLAN" or "SITE/GRADING PLAN".
2. Add note: "Depress all landscaped areas a maximum of 6" for water harvesting"
3. Correct the lot number on the plan.
4. Per general note 8 of the final plat, slopes equal to or greater than 25% shall not be used for development. Please revise plans to reflect this.
5. Please provide a table of contour lengths for ACS review.
6. Slopes of 2H:1V or greater should include grouted rip-rap.
7. Flow arrows, grades and flow rates within and adjacent to site to show drainage scheme.


If you have any questions, I can be reached at 791-5550, or pmachad2@ci.tucson.az.us
Paul Machado
Senior Engineering Associate
12/10/2002 ANY FLOODPLAIN REVIEW Approved
12/11/2002 PATRICIA GILBERT NPPO REVIEW Approved
12/11/2002 DAN CASTRO ZONING REVIEW Denied Grading plan may not be approved until site plan is approved and grading plan is approved by Engineering and Landscape Sections.
12/12/2002 MVALDEZ1 NPDES REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/12/2002 MONICA VALDEZ OUT TO CUSTOMER Completed