01/31/2003 PETER MCLAUGHLIN ZONING REVIEW Approved
01/31/2003 ELIZABETH EBERBACH FLOODPLAIN REVIEW Approv-Cond TO: Arden Ranshaw, Tetra Tech Inc.
SUBJECT: Starr Pass Resort Grading Plan, Floodplain, & Engineering Review
REVIEWER: Elizabeth Eberbach
DATE: January 31, 2003
ACTIVITY NUMBER: T02BU02876

SUMMARY: Engineering recommends approval for a grading permit with the following conditions of approval for the grading permit. Engineering also recommends a concurrent approval of the floodplain use permit application. The drainage addenda were reviewed for grading purposes only.

GRADING PERMIT CONDITIONS OF APRROVAL
1) The grading permit will be for earthwork and grading construction within the approved grading limits.
2) See the approved GRADING PLANS FOR STARR PASS RESORT HOTEL (dated 1/31/03), HDZ variance case # CO-24-98-1, Terracon geotechnical addenda (dated 2/25/99 and 1-29-03), and drainage addenda (dated 1/31/03), including ADDENDUM TO DRAINAGE REPORT FOR MARRIOTT STARR PASS RESORT HOTEL DEVELOPMENT PLAN (dated 11/12/02) for drainage improvements for perimeter roadway and detention basin.
3) Additional drainage addenda, geotechnical addenda, floodplain use permit applications, or resubmittals may be required for review and approval by the City of Tucson Development Services Engineering Division, if the following occurs or is proposed:
a) additional disturbance onsite;
b) changes in the grading;
c) changes in drainage design;
d) further floodplain encroachment;
e) any conflicts with grading or drainage between this approved grading plan and the roadway construction plans;
f) grading construction phasing;
g) changes in locations for construction entrances;
h) changes in locations for construction equipment storage areas.
4) All roof drainage shall have grading and erosion protection at outlets to provide positive flow away from structures.
5) The engineer of record shall design safety barriers along roadway for access to grand ballroom.
6) This project shall conform to 404 permitting requirements and all disturbances shall be in approved areas and shall not encroach the 404 limits unless exempted through 404 permit.
7) Crossing number 6 shall be spanned, with a temporary construction crossing located and with only that width of 404 limit disturbance as shown on the approved grading plans.
8) Construction fencing shall be maintained at approved grading limits to clearly define the construction site and no disturb areas for locations where grading limits are in close proximity to 404 limits.
9) A copy of the As-builts are required to be submitted to City of Tucson Development Services Engineering Division.
If you have any questions, I can be reached at 791-5550, extension 2204.
Elizabeth Eberbach, PE
Civil Engineer
Engineering Section
Development Services
01/31/2003 ELIZABETH EBERBACH ENGINEERING REVIEW Approv-Cond TO: Arden Ranshaw, Tetra Tech Inc.
SUBJECT: Starr Pass Resort Grading Plan, Floodplain, & Engineering Review
REVIEWER: Elizabeth Eberbach
DATE: January 31, 2003
ACTIVITY NUMBER: T02BU02876

SUMMARY: Engineering recommends approval for a grading permit with the following conditions of approval for the grading permit. Engineering also recommends a concurrent approval of the floodplain use permit application. The drainage addenda were reviewed for grading purposes only.

GRADING PERMIT CONDITIONS OF APRROVAL
1) The grading permit will be for earthwork and grading construction within the approved grading limits.
2) See the approved GRADING PLANS FOR STARR PASS RESORT HOTEL (dated 1/31/03), HDZ variance case # CO-24-98-1, Terracon geotechnical addenda (dated 2/25/99 and 1-29-03), and drainage addenda (dated 1/31/03), including ADDENDUM TO DRAINAGE REPORT FOR MARRIOTT STARR PASS RESORT HOTEL DEVELOPMENT PLAN (dated 11/12/02) for drainage improvements for perimeter roadway and detention basin.
3) Additional drainage addenda, geotechnical addenda, floodplain use permit applications, or resubmittals may be required for review and approval by the City of Tucson Development Services Engineering Division, if the following occurs or is proposed:
a) additional disturbance onsite;
b) changes in the grading;
c) changes in drainage design;
d) further floodplain encroachment;
e) any conflicts with grading or drainage between this approved grading plan and the roadway construction plans;
f) grading construction phasing;
g) changes in locations for construction entrances;
h) changes in locations for construction equipment storage areas.
4) All roof drainage shall have grading and erosion protection at outlets to provide positive flow away from structures.
5) The engineer of record shall design safety barriers along roadway for access to grand ballroom.
6) This project shall conform to 404 permitting requirements and all disturbances shall be in approved areas and shall not encroach the 404 limits unless exempted through 404 permit.
7) Crossing number 6 shall be spanned, with a temporary construction crossing located and with only that width of 404 limit disturbance as shown on the approved grading plans.
8) Construction fencing shall be maintained at approved grading limits to clearly define the construction site and no disturb areas for locations where grading limits are in close proximity to 404 limits.
9) A copy of the As-builts are required to be submitted to City of Tucson Development Services Engineering Division.
If you have any questions, I can be reached at 791-5550, extension 2204.
Elizabeth Eberbach, PE
Civil Engineer
Engineering Section
Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
01/31/2003 LISA LESNY OUT TO CUSTOMER Completed