Permit Number: T02BU02822
Parcel: 136327940

Review Status: Completed

Review Details: GRADING

Permit Number - T02BU02822
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/10/2002 PAUL MACHADO ENGINEERING REVIEW Denied To: Nadine Leonard
TJ Bednar
4846 N. Davis Ave. Tucson, Arizona 85705
SUBJECT: Lot 137 of Rancho Cancion West
T02BU02822 (First submittal)
T14S, R15E, Section 36

RESUBMITTAL REQUIRED: Grading Plan

The Grading Plan (GP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:

1. Grading plan clearly marked "GRADING PLAN" or "SITE/GRADING PLAN".
2. Add note: "Depress all landscaped areas a maximum of 6" for water harvesting"
3. Per general note 8 of the final plat, slopes equal to or greater than 25% shall not be used for development. This also includes the building pad area. A copy of the final plat has been provided. Please revise plans to reflect no development in these areas.
4. Please provide a table of contour lengths and calculations for ACS review.
5. Flow arrows, grades and flow rates within and adjacent to site to show drainage scheme.
6. Please provide proposed disturbed area in square feet on plans.


If you have any questions, I can be reached at 791-5550, or pmachad2@ci.tucson.az.us
Paul Machado
Senior Engineering Associate
12/10/2002 PATRICIA GILBERT NPPO REVIEW Denied Please add a general note that all grading will conform to the city of Tucson Development Standard 9-04 Hillside Development Site Improvment.

Please revise general note #1and 3 to read City of Tucson Zoning Code.

The portions of the site or lot to be left ungraded are to remain undisturbed and are not to be used for stockpiling of materials or excess fill, construction vehicle access, storage of vehicles during construction, or similar uses. Temporary fencing is required at the grading limit in order to prevent encroachment into the natural areas. Please show on the plan the location of the temporary fencing. Refer to DS 9-04.3.1.A.2.

A pre-permit inspection is required to check tempoary fencing. To schedule please call 791-5640, ext. 1140.
12/10/2002 ANY FLOODPLAIN REVIEW Approved
12/16/2002 MSTPAUL1 NPDES REVIEW Passed
12/16/2002 MICHAEL ST. PAUL ZONING REVIEW Needs Review Floodplain approval required before Zoning review.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/16/2002 LISA LESNY OUT TO CUSTOMER Completed