Permit Number: T02BU02652
Parcel: Unknown

Review Status: Completed

Review Details: GRADING

Permit Number - T02BU02652
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/15/2002 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering Comments, 10/15/2002

1- Separate the words "obtain" and "all" in grading note #9.
2- Complete the Grading Plan Case number on all sheets.
3- Provide the subject site administrative/site address.
4- Provide all curb return radii.
5- The Development Plan is not approved yet.
10/15/2002 LAITH ALSHAMI FLOODPLAIN REVIEW Denied Laith Alshami, Floodplain Comments, 10/15/2002

1- State the numbers of proposed scuppers at the different locations.
2- The number, location and size of several drainage related curb openings are different from the drainage report. Revise to match the report or justify the change.
3- Provide rip rap spillways at the proposed curb openings.
4- The grading plan shows rip rap spillways at different locations without curb openings.
5- Call out perimeter walls if any.
6- Label the proposed sidewalk scupper at the northwest corner of Building #3.
7- It appears from cross-section B/5, the drainage scheme shown on the grading plan is different from the one shown in the drainage report. Justify the modification or revise.
8- The plan shows two type 1 scupper locations around building #1 but does not show the scuppers. Revise.
9- Security barriers appear to be needed on Cross Section A/5. Revise.
10- Cross Section B/5 appears to be different from the cross section in the development plan.
11- Provide a minimum 8" thick concrete for all proposed grouted rip rap.
12- Provide full dimensions for the proposed detention/retention basins.
13- Provide percolation test to verify that the proposed retention basins will operate as designed.
10/23/2002 LOREN MAKUS NPDES REVIEW Denied Provide 3 copies of Stormwater Pollution Prevention Plan for Review and acceptance.
10/25/2002 PATRICIA GILBERT NPPO REVIEW Denied An approved development plan is required prior to plan approval.

Please submit approved NPPO plan or approved documentation of an exception to NPPO.

Once the development plan is approved, a pre-permit inspection may be required. To schedule please call 791-5550, ext. 1140.
10/25/2002 MICHAEL ST. PAUL ZONING REVIEW Denied Engineering, Floodplain and NPPO approvals required.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/28/2002 TAMI ACHONG OUT TO CUSTOMER Completed