Review Details: GRADING

Permit Number - T02BU02650
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2002 PAUL MACHADO ENGINEERING REVIEW Denied To: Greg Carlson Engineering, L.L.C. 330 S. Toole Ave., #500 Tucson, Az. 85701
SUBJECT: Main Gate Phase 3
T02BU02650 (First submittal)
T14S, R14E, Section 07

RESUBMITTAL REQUIRED: Grading Plan

The Grading Plan (GP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:

1. Add note: "Depress all landscaped areas a maximum of 6" for water harvesting"
2. Keynote nos. 16 and 17 call out a transition of 8" to 1.5' and reverse. Please list what kind of transition.
3. Addministrative address/site address.
4. A private improvement agreement may be necessary for work performed within the Right-of-way. Contact Department of transportation at (520) 791-4249 for information.
5. Delineate 100-year W.S.E.L., Floodplain and erosion hazard setback.
6. Call out peak discharges entering and exiting the site.

If you have any questions, I can be reached at 791-5550, or pmachad2@ci.tucson.az.us
Paul Machado
Senior Engineering Associate
10/30/2002 ANY FLOODPLAIN REVIEW Approved See engineering folder.
11/01/2002 PATRICIA GEHLEN ZONING REVIEW Denied 11/1/02
Zoning
Please provide a copy of the stamped approved development plan with the resubmittal of these plans
11/04/2002 MSTPAUL1 NPDES REVIEW Passed
11/04/2002 PATRICIA GILBERT NPPO REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/04/2002 TAMI ACHONG OUT TO CUSTOMER Completed