Review Date Reviewer's Name Type of Review Description Status Comments
09/05/2002 DAVID RIVERA ZONING REVIEW Needs Review Zoning will approve the grading plan after the Engineering and Landscape reviewer have approved the plan.
10/04/2002 PAUL MACHADO ENGINEERING REVIEW Denied To: George Holguin, AIA
Architect
PO Box 13152

SUBJECT: 5330 E. Bellevue street
Grading Plan T02BU02371 (First Review)
T14S, R14E, Section 2

RESUBMITTAL REQUIRED: GP

The Grading Plan (GP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:

1. Add Administrative/Site address on the cover sheet.
2. Change title to read "Site/Grading Plan" in the title block.
3. Add Activity number to plans.
4. Add note "All grading shall conform to the latest edition of the 2000 IBC"
5. A private improvement agreement may be necessary for work performed within the Right-of-way. Contact Department of transportation at (520) 791-4249.
6. Show cross sections of the basins and dimension on the plans.
7. The basin slopes are at 2:1. These slopes shall have hand placed rip-rap.

Drainage Report:
The Drainage report is approved.

If you have any questions, I can be reached at 791-5550 or pmachad2@ci.tucson.az.us

Paul Machado
Senior Engineering Associate,
10/04/2002 ANY FLOODPLAIN REVIEW Approved
10/07/2002 LOREN MAKUS NPDES REVIEW Approved
10/08/2002 JOE LINVILLE NPPO REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/10/2002 LISA LESNY OUT TO CUSTOMER Completed