Permit Number: T02BU02163
Parcel: 103090180

Review Status: Completed

Review Details: GRADING

Permit Number - T02BU02163
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2002 DAN CASTRO ZONING REVIEW Denied Grading plan may not be approved until grading plan is approved by all other sections.
11/22/2002 BLANCA ESPINO NPDES REVIEW Passed
11/22/2002 BLANCA ESPINO ENGINEERING REVIEW Denied GRADING
1. As per the Grading Plan, note 11 needs correction. It should read Chapter 36 of the International Building Code.

2. Indicate limits of the 100-year floodplain on site plan or indicate with a notation stating that the whole site is in a floodplain/zone/panel number/effective date. D.S. 2-02.2.1.15

3. Indicate site address on grading plan.

4. Indicate a cross section across property line showing clear acceptance of off-site flow.

5. Correct and revise finish floor elevations.

6. Call out surface paving material on grading plan.

7. Indicate limits of the 100-year floodplain on site plan or indicate with a notation stating that the whole site is in a floodplain/zone/panel number/effective date.

8. Show the 100-year flood peak discharges entering and exiting site.

9. Provide Maintenance Note for on site detention/retention basin. A minimum of one 15-foot-wide vehicular access ramp shall be provided into each basin. The maximum roadway or access ramp slope shall not exceed 15 percent. Alternate means of access will be reviewed by the City Engineer on a case-by-case basis. SMDDFM 14.3.3 & 4 and 2.3.1.6.C
11/22/2002 BLANCA ESPINO FLOODPLAIN REVIEW Denied SEE ENGINEERING COMMENTS
11/26/2002 JOE LINVILLE NPPO REVIEW Denied Approved site plan and NPPO Pre Permit Inspection required prior to approval. Call 791-5640 Ext. 1140 to schedule.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/27/2002 MONICA VALDEZ OUT TO CUSTOMER Completed