Permit Number: T02BU01811
Parcel: 115172340

Review Status: Completed

Review Details: GRADING

Permit Number - T02BU01811
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/02/2002 JIM TATE ENGINEERING REVIEW Denied The following items must be revised or added to the Grading Plan. Please include a letter with the next submittal addressing how all the engineering and flood plain comments have been addressed.

1. A copy of the stamped approved Site Plan must be included with the Grading Plan submittal.

2. The Site Plan is currently being reviewed. Changes made to the Site Plan must be reflected on the Grading Plan. The Site Plan must be approved prior to Grading Plan approval. Changes made to the Site Plan could result in additional Grading Plan comments.

2. Show appropriate dimensions on the sections. Dimension width of sidewalk, distance from curb to sidewalk, etc.

3. The Grading Plan scales 8 ft. from face of curb to property line on Apache. The Site Plan scales 10 ft.

4. The Drainage Report specifies that the drainageway from the basin weir to the street scupper will be 2 ft. wide and 6 inches deep. The Grading Plan shows the width as 4 ft. with an indeterminate depth.
07/02/2002 JAMES TATE FLOODPLAIN REVIEW Denied See Engineering folder comments.
07/16/2002 PETER MCLAUGHLIN ZONING REVIEW Denied
07/23/2002 JOE LINVILLE NPPO REVIEW Denied Approved native plant preservation required for review.
07/25/2002 MSTPAUL1 NPDES REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
07/29/2002 DELMA ROBEY OUT TO CUSTOMER Completed