Permit Number: T02BU01385
Parcel: 13405116C

Review Status: Completed

Review Details: GRADING

Permit Number - T02BU01385
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2002 DAN CASTRO ZONING REVIEW Denied
06/07/2002 DOUG WILLIAMS NPDES REVIEW Passed
06/07/2002 DOUG WILLIAMS ENGINEERING REVIEW Denied Grading Plan may not be approved until the Drainage Report and Site Plan are approved. Include redlines with resubmittal.
06/07/2002 JOE LINVILLE NPPO REVIEW Denied Approved site and native plant preservation plans are required. A NPPO pre permit inspection will also be required prior to grading.
06/07/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Denied See comments under Site review comments (T02CM02336) and redlines on plan sheets 1-3. Include redlines with resubmittal.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/17/2002 TAMI ACHONG OUT TO CUSTOMER Completed