Permit Review Detail
Review Status: Completed
Review Details: GRADING
Permit Number - T02BU01385
Review Name: GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/17/2002 | DAN CASTRO | ZONING | REVIEW | Denied | |
| 06/07/2002 | DOUG WILLIAMS | NPDES | REVIEW | Passed | |
| 06/07/2002 | DOUG WILLIAMS | ENGINEERING | REVIEW | Denied | Grading Plan may not be approved until the Drainage Report and Site Plan are approved. Include redlines with resubmittal. |
| 06/07/2002 | JOE LINVILLE | NPPO | REVIEW | Denied | Approved site and native plant preservation plans are required. A NPPO pre permit inspection will also be required prior to grading. |
| 06/07/2002 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Denied | See comments under Site review comments (T02CM02336) and redlines on plan sheets 1-3. Include redlines with resubmittal. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/17/2002 | TAMI ACHONG | OUT TO CUSTOMER | Completed |