Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T02BU01262
Parcel: 14016003F

Review Status: Completed

Review Details: GRADING

Permit Number - T02BU01262
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2002 JIM TATE ENGINEERING REVIEW Denied The following items must be revised or added to the Grading Plan. Please include a letter with the next submittal addressing how all the engineering and flood plain comments have been addressed.

1. The top of cut slopes must be a minimum of two feet from the property line. Please show on the plan that the detention basin is at least two feet from the property line. (IBC Chapter 36, Section 14.2).

2. A copy of the stamped approved Development Plan must be included with the Grading Plan submittal before the Grading Plan can be approved.
05/03/2002 MSTPAUL1 NPDES REVIEW Passed
05/03/2002 MICHAEL ST. PAUL ZONING REVIEW Denied See Engineering.
05/03/2002 JAMES TATE FLOODPLAIN REVIEW Denied See Engineering comments.
05/06/2002 JOE LINVILLE NPPO REVIEW Approved exc.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/06/2002 CINDY AGUILAR OUT TO CUSTOMER Completed