Permit Number: T02BU01097
Parcel: 11009006L

Review Status: Completed

Review Details: GRADING

Permit Number - T02BU01097
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2002 DOUG WILLIAMS ENGINEERING REVIEW Denied 1. Indicate area to be disturbed for reseeding bond determination.

2. Depict grading limits on the plan.
05/03/2002 PETER MCLAUGHLIN ZONING REVIEW Denied
05/03/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
05/06/2002 MSTPAUL1 NPDES REVIEW Passed
05/06/2002 JOE LINVILLE NPPO REVIEW Denied Approved site/development plans and Native Plant Preservation Plans must accompany grading submittal. Add information to the plans regarding the native plant preservation plan. A NPPO Pre-permit inspection will be required prior to permit issuance.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/08/2002 TAMI ACHONG OUT TO CUSTOMER Completed